SECTION 1 4-MicroVersaTrip™ Plus and MicroVersaTrip™ PM Trip Units
1 4.4 TRIP UNIT REMOVAL AND REPLACEMENT
The programmer mounts to the upper left of the breaker
as shown in Fig. 1 1 5. It mounts to the bracket assembly
shown in Fig. 82. Guide pins on the bracket mate with the
holes on either side of the programmer connector. They
provide the necessary alignment for the connector en
gagement. The locking lever engages with the pin which
is assembled to the programmer frame and secures the
programmer to the mounting bracket. When a trip unit is
replaced , the locking arm snaps back i nto place to indi
cate proper alignment.
WARNING:
Always de-energize Type AKR circuit break
ers before attempting to remove or replace the trip unit.
Because of the exposed location of the trip unit, failure to
observe this warning may result in equipment damage or
personal injury, including death.
FIG. 1 13 PROGRAMMER SECONDARY
CONNECTOR
Socket
Class
No.
5
+
Zone
Zone
6
-
Inputs
Selective
Interlock
7
+
Zone
8
-
Outputs
1 1
-
1 2
+
Hom net
9
Spare
1 0
vc
MVT-PM
1
VB
4
VA
2
24
Ret
3
+
24 VDC
NOTE LOCA fiON OF PIN #1
FIG. 1 14 PROGRAMMER SECONDARY
CONNECTOR PIN LOCATIONS FOR ZONE
SELECTIVE INTERLOCK AND MVT -PM
79