SECTION 9-Fused Breakers (Cont.)
1 . Special Z SOOA Fuse
Z . Di sconnect Key
3 . Heat Sink
4 . Upper Barrier
5 . Primary Di sconnect
FIG. 53 AKRU 50 WITH SPECIAL
2500 AMP FUSE
CAUTION:
WHEN REPLACING THE FUSE IN THE
LEFT POLE (FRONT VIEW) OF THE BREAKER,
NOTE PAR TICULARL Y THA T THIS FUSE IS
MOUNTED DIFFERENTLY THAN THE OTHER TWO
FUSES. AS SHOWN IN FIG.
54,
FOR THIS PHASE
THE FUSE IS ROTATED
180
DEGREES ABOUT
ITS AXIS SO THA T I TS INBOARD TANG IS
POSITIONED
THE BREAKER STUD.
THIS TANG IS OFFSET WITH RESPECT TO THE
OPPOSITE END SO THA T ROTATING THE FUSE
DOES NOT ALTER THE POSITION OF THE PRI
MARY DISCONNECT.
0
FRONT OF BREAKER
FUSE TANGS
BREAKER
STUD
POSITIONED ON TOP
OF BREAKER STUD
1 TANG BOLT•
HOLES
IN USE
0 0
2500A. FUSE
CAT. NO.
GF9F2500 AK
0 0
FOR THIS POLE ONLY,
FUSE IS ROTATED
1 80
TO POSITION TANG
BENEATH
STUD
0 0
PRIMARY DISCONNECT ASSEMBLY (SEE FIG.
1 3)
MOUNTS DIRECTLY ON OUTBOARD FUSE TANG
FIG. 54
AKRU 50-2500A FUSE TANG POSITIONS
TABLE 6
FUSES FOR AKRU BREAKERS
NEMA
Gould Shawmut
Fuse
Breaker
Cat. Nos.
Clan
Ampere
600V
Rating
60 Hz
30
Fuse
Limiter
-
300'
A4J
300
-
-
350'
A4J 350
-
J
-
400'
A4J 400
-
I
450
A4J 450
-
500
A4J
500
-
600
A4J 600
-
I
800
A48Y 800
A4BX 800
L
1 000
A4BY 1 000BG
A4BX 1 000BG
1 200
A4BY 1 200BG
A4BX 1 200BG
1 600
A48Y 1 600BG
A4BX 1 600BG
-
2000
A48Y 2000BG
A4BX 2000BG
Spec1al
-
2500
-
A4BX 2500GE
•
Mounting adapter requ•red - see
F
19
52
42
www
. ElectricalPartManuals