Current Transformer Mounting
Hardware
Provides the necessary mounting hardware for mounting
applicable current transformers in the substructure.
Programmer Secondary Disconnect
Required when programmer on breaker has zone selective
interlocking .
Door I nterlock Kit
Provides for interlocking door (hinges left or right) such that
breaker must be in the disconnect position before door can
be opened. Interlock is defeatable for authorized access.
200UA
"T"
Connector
(For 1600A and 2000A substructures.)
Provides alternate means for bus connecting to the
substructure.
Shutter Kit
Shutters to cover primary disconnects when breaker is
moved to the test position.
Provision s for Padlocking Breaker in Disconnect Positio n
Padlock assembly engages with the breaker mounting
bracket in the substructure. It prevents the breaker from
being moved from the disconnected to the test or connected
positions. The padlock slot will accept three ,
3fa
inch
diameter hasps.