B R EAKER MOUNTED - R I GHT S I D E
8
EQU I PM E N T MOU NTED
FIG. 86 - NEUTRAL SENSOR SECONDARY
DISCONNECT
S i n ce the neutral senso r is mounted separately
from the breaker, a d i sconnect means i s req u i red to
con nect its output to the breaker. Fig. 86 shows the
breaker and e q u i pment mou nted 4th w i re secondary
d iscon nect u sed with the M i croVersaTri p system.
1 2.2.1
REPLACEMENT OF CURRENT
SENSORS
Referring to Fig. 87, replacement of MicroVersaTrip cur
rent sensors is accompl ished as fol lows:
a) Disconnect the programmer harness from the ter
minal board, removing cable ties as necessary.
b) At the rear of the breaker, remove the two Allen head
screws to separate the stud connector from the contact
pivot block.
c) Loosen the clamping bolt and remove the stud con
nector. Lift out the sensor and its tap terminal board.
The sensor may be prevented from slipping off the sen
sor stud by adjacent accessories. If this exists, the sensor
stud must be removed from the breaker base. The stud
assembly is secured to the base with four bolts which are
accessible from the rear of the breaker.
d) When replacing the stud connector, tighten the Al len
head screw to 250 ± 10 i n-lbs. Tighten the clamping bolt
as follows:
AKR 30/30H 1 20 ± 1 0 in-lbs
AKR 50/50H 470 ± 1 0 in-lbs
AKRT 50/50H 470 ± 1 0 in-lbs
e) When replacing the programmer harness to the
phase sensors verify that the winding polarity is maintain
ed, white wire with ring terminal to COMMON termi nal
(right hand terminal, see Fig. 83).