TABLE 23 1NSTANTANEOUS UNDERVOLTAGE DEVICE SETTINGS
PICK UP VOLTAGE RANGE
COI L
UVR ONLY
UVR I N STALLED
DROP OUT
RATING
MECHANISM RESET
RANGE
24 VDC
1 8 . 20
1 6 . 20
7 . 8.3
48 VDC
36 . 41
32 - 41
1 4 - 1 7
1 25 VDC
1 06 - 1 10
1 04 - 1 1 0
38 - 43
1 55 VDC
1 09 - 1 32
1 01
•
1 32
47 - 93
250 VDC
212 - 221
209 - 221
75 - 85
1 20 VAC
1 02 - 1 06
1 00 - 1 06
36 - 72
208 VAC
1 56 . 1 76
1 36 - 1 76
62 - 1 25
240 VAC
206 - 212
200 . 21 2
72 . 1 44
380 VAC
285 - 323
247 - 323
1 1 4 - 223
480 VAC
360 - 408
312 - 408
1 44 - 288
575 VAC
431 - 488
374 - 488
1 73 . 345
TABLE 24 TIME-DELAY UNDERVOLTAGE DEVICE SETTINGS
DELAY
PICK UP RANGE
UVR INSTALLED
DROP OUT
U N IT
UVR ONLY
MECHANISM RESET
RAN G E
VOLTAGE
VDC
NO PICK UP
PICK UP
1 25 VDC
77 - 85
50
90 - 95
250 VDC
M IN IMUM
208/240 VAC
1 25 - 1 40
90
1 60 - 165
POSSIBLE
79