2-68
ALPS Advanced Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
612
51GPICKUP
51G Pickup Setting
0.20 to 15.0 amps
step 0.01
0.04 to 3.0 amps
step 0.01
613
51GPCKUPFF
51G Pickup during fuse failure
0.20 to 15.0 amps
step 0.01
0.04 to 3.0 amps
step 0.01
614
51GCURVE
51G Curve
INV, V-INV, E-INV, CUSTOM, DEFT
615
51GTIMDIAL
51G Time Dial
0.5 to 10.0 step 0.1
616
DEFTIMDELY
Definite Time Delay
0.5 to 30.0 sec. step 0.1
617
51G_RESET
51G Reset Characteristic
FAST, EM
VOLTAGE
701
RATEDVOLTS
Rated Per Unit Voltage
100, 105,110,115, 120 volts
702
PHASEOVER
Select Phase Overvoltage
NO, YES
703
PHOVPICKUP
Phase Overvoltage Pickup
0.0 to 1.4 p.u. volts step 0.01
704
PHOVTMDLY
Phase Overvoltage Time Delay
0.0 to 10.0 sec. step 0.01
705
V1OVER
Select Positive Sequence
Overvoltage (Overvoltage Model
Only)
NO, YES
706
V1OVINSTPU
Instantaneous Positive Sequence
Overvoltage Pickup (Overvoltage
Model Only)
1.0 to 1.4 p.u. volts step 0.01
707
V1OVTIMPU
TOV Positive Sequence
Overvoltage Pickup (Overvoltage
Model Only)
1.0 to 1.4 p.u. volts step 0.01
708
V1OVTIMDLY
Positive Sequence Overvoltage
Time Delay (Overvoltage Model
Only)
0.0 to 10.0 sec. step 0.01 sec.
709
V1COMP
Compensated Positive Sequence
Overvoltage (Overvoltage Model
Only)
NO, YES
710
V1COMPRCH
Compensated Positive Sequence
Overvoltage Impedance
(Overvoltage Model Only)
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
711
V1COMPINPU
INST Compensated Positive
Sequence OV Pickup
(Overvoltage Model Only)
0.0 to 1.4 p.u. volts step 0.01
712
V1COMPTDPU
TOV Compensated Positive
Sequence OV Pickup
(Overvoltage Model Only)
0.0 to 1.4 p.u. volts step 0.01
713
V1COMPTDLY
Compensated Positive Sequence
OV Time Delay (Overvoltage
Model Only)
0.0 to 10.0 sec. step 0.01
714
FUSEFAIL
Potential Fuse Failure Blocking
NO, YES
BLK RECLOS
801
ALL_BELOW
Block reclosing for any function
NO, YES
802
OUTOFSTEP
Block for Out of Step
NO, YES
803
ALL_3_Z2PH
Block for 3 phase faults
NO, YES
804
50G_BLOCK
Block for 50G trip
NO, YES
805
Z2TIMETRIP
Block for Z2 Time Delayed Trip
NO, YES
806
Z3TIMETRIP
Block for Z3 Time Delayed Trip
NO, YES
807
Z4TIMETRIP
Block for Z4 Time Delayed Trip
NO, YES
808
Z1PHASTRIP
Block for any Z1 Phase Fault
NO, YES
809
ANYZ2PHASE
Block for any Z2 Phase Fault
NO, YES
810
CONFGTRIP
Block For Configurable Trip Logic
NO, YES
Table 2–13: PROTECTION SETTINGS DATA SHEET (Sheet 3 of 7)
NO.
MNEMONIC
DESCRIPTION
RANGE (5A)
RANGE (1A)
USER
SETTING
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.