12-2
ALPS Advanced Line Protection System
GE Power Management
12.1 INTRODUCTION
12 ASCII COMMUNICATIONS
12
Table 12–2: ASCII COMMAND LIST (Sheet 1 of 5)
ASCII
COMMAND
MNEMONIC
COMMAND DESCRIPTION
LOWEST
LEVEL
PASSWORD
NEEDED
RELAY PROMPT
USER
RESPONSE
LOGIN
Login to the relay
NONE
Unit ID?
Password?
Reports the access level granted or that the
password entered is INVALID
Relay ID number;
up to 10 character
password
QUIT
Logs out from the relay,
displays the relay status,
and returns the privilege
level to VIEW for the relay
port used.
VIEW
Press ENTER to continue
Do you want to logout?
You have logged out from the relay
Press the enter
key; Y or N
PASSword
Change the passwords
used by ALPS-Link and
ASCII; MMI passwords are
not affected by this
command
Level equal to
the password
being
changed
Enter Current Password
Enter New Password
Re-enter New Password
Password changed or INVALID; password not
changed
old password;
new password;
new password
VALues
Display the present values
of voltages, currents, watts,
Vars, etc., including Breaker
Health in the second
screen. Press ENTER to
see the second screen
VIEW
Present Values
VA rms: V
VB rms: V
VC rms: V
VA: V degs
VB: V degs
VC: V degs
Watts: KW
P ow er Factor
S etting G roup N um ber:1
Breaker 1: Closed
Breaker Health
Phase A accumulated
Amps: 45.2 A
Phase B accumulated
Amps: 11.1 A
Phase C accumulated
Amps: 25.7A
IA rms: A
IB rms: A
IC rms: A
In rms: A
IA: A degs
IB: A degs
IC: A degs
In: A degs
Vars: kVar
Frequency: Hz
No. of Breakers: 2
Breaker 2: N/A
Breaker Operations: 129
None
READings
Display the present values
of voltages, currents, watts,
Vars, etc., and update them
once per second. The ESC
key stops the update. No
Breaker Health is displayed.
FAUlts
Display fault reports. The list
of available faults is
displayed first then a
number is chosen to view a
particular fault
VIEW
FLTNO DATE TIME TRIP
FAULT DISTANCE
TYPE
TYPE
1
07/09/98
EXT
AG
0.2mi
15:32:23.6833
Enter Fault Number (press ESC to quit): 1
Report for Fault No: 1
TRIP DATE: 07/03/98
TRIP TIME: 16.32.23.6833
Trip Type(s): Z1
Fault Type: ABG
Relay Operating Time: 488 ms
Breaker Operating Time: 1152 ms
Distance: 9999 miles
ITEM
A
B
C
D
Prefault Current (A)
0.00
0.00
0.00
0.00
Fault Current (A)
0.00
0.00
0.00
0.00
Fault Voltage (kV)
0.00
0.00
0.00
0.00
Press ENTER to Continue
List of Fault Events:
TIME
EVENT
16:32:23.7025
Oscillography Capture
16:32:23.7041
RMS Oscillography Data
Press Y to get oscillography data
Press ESC to quit
Press Any Key to continue
Press E for
expanded mode,
ESC to end
Two digit number,
1 to 16