GE Power Management
ALPS Advanced Line Protection System
C-13
APPENDIX C C.3 POINT LISTS
C
C.3.5 ANALOG INPUT, ANALOG INPUT CHANGE
Table C–6: POINT LIST: OBJECTS 30 & 32 (Sheet 1 of 6)
ANALOG INPUT (OBJECT 30)
ANALOG INPUT CHANGE (OBJECT 32)
INDEX
DESCRIPTION
EVENT CLASS
ASSIGNED TO
FORMAT/
UNITS
REMARKS
0 Phase A RMS Current Class 2 F1
Amp Note 2
1 Phase B RMS Current Class 2 F1 Amp Note 2
2 Phase C RMS Current Class 2 F1 Amp Note 2
3 Neutral RMS Current Class 2 F1 Amp Note 2
4 Phase A RMS Voltage Class 2 F2 Amp Note 2
5 Phase B RMS Voltage Class 2 F2 Volt Note 2
6 Phase C RMS Voltage Class 2 F2 Volt Note 2
7 Phase A Current Amplitude Class 2 F1 Amp Note 2
8 Phase A Current Angle Class 2 F4 Deg. Note 2
9 Phase B Current Amplitude Class 2 F1 Amp Note 2
10 Phase B Current Angle Class 2 F4 Deg. Note 2
11 Phase C Current Amplitude Class 2 F1 Amp Note 2
12 Phase C Current Angle Class 2 F4 Deg. Note 2
13 Neutral Current Amplitude Class 2 F1 Amp Note 2
14 Neutral Current Angle Class 2 F4 Deg. Note 2
15 Phase A Voltage Amplitude Class 2 F2 Amp Note 2
16 Phase A Voltage Angle Class 2 F4 Deg. Note 2
17 Phase B Voltage Amplitude Class 2 F2 Amp Note 2
18 Phase B Voltage Angle Class 2 F4 Deg. Note 2
19 Phase C Voltage Amplitude Class 2 F2 Amp Note 2
20 Phase C Voltage Angle Class 2 F4 Deg. Note 2
21 Watts Class 2 F3 Watts Note 2
22 Vars Class 2 F3 Vars Note 2
23 Power Factor Class 2 F1 Note 2
24 Frequency Class 2 F1
25 Status – CPU Status Word 1 Class 2 F9
26 Status – CPU Status Word 2 Class 2 F9
27 Status – ANI Status Class 2 F10
28 Status – DSP Status Class 2 F11
29 Status – Misc. Status Word 1 Class 2 F12
30 Status – Misc. Status Word 2 Class 2 F12
31 Fault 1 Date (Lower 16-Bits) Class 2
32 Fault 1 Date (Middle 16-Bits) Class 2
33 Fault 1 Date (Upper 16-Bits) Class 2
34 Fault 1 Type Class 2 F5
35 Fault 1 Trip Type F6
36 Fault 1 Distance F2
37 Fault 1 Relay Operating Time Class 2 F4
38 Fault1 Breaker Operating Time Class 2 F4
39 Fault1 – Phase A Prefault Current Class 2 F1
40 Fault1 – Phase B Prefault Current F1
41 Fault1 – Phase C Prefault Current F1
42 Fault1 – Neutral Prefault Current F1
1
,
2
,
3
,
4
,
5
,
6
See Table Notes following the Table