4-2. Parameter Blocks configuration
4. Programming
Mode Selection
The ASTAT Plus includes a large number of parameters which are divided in four
blocks: Monitor, Calibration, Basic and Advanced. The parameters of each group can be
displayed or skipped according the selection done in parameter "G".
The monitor parameters are always displayed regardless of the mode selected
Settings in parameter "G"
G
xxx
The Monitor parameters are always displayed,
whichever are the settings in parameter "G".
G
CAL
The Calibration parameters are displayed
G
BAS
The Basic parameters are displayed
G
ADV
The Advanced parameters are displayed
G
ALL
All parameters are displayed
Monitoring
Parameters
Calibration
Parameters
Basic
Parameters
Advanced
Parameters
G
CAL
G
ALL
G
BAS
G
ADV
There is a quick way to search automatically the parameter "G" by pressing
and
Keys. "Gxxx" will be shown on the display.
Once the parameter "G" is displayed, choose the value desired by pressing
or
Keys. The display will sequence "GBAS", "GCAL", "GADV" and
"GALL" values repeatedly. The actual value displayed can be stored in a temporal memory buffer by pressing
key.
Values stored in the temporal memory are lost upon control power loss, unless these are saved in the permanent E2PROM memory through parameter "W".
Additional indications are given in page 4-4
The above is an example given for parameter "G", but all ASTAT Plus parameters can be modified from its default factory value proceeding in similar way.
Searching and Setting Parameters
The ASTAT Plus displays the parameters sequentially while depresing the
key and pushing repeteadly
or
keys.Proceed in this way untill
the parameter "G" is displayed.
C / V
C / V
Parameter layout
Monitor
parameters
U
Line Voltage
Voltage Calibration
Unit frame
Current Calibration
t
UF
m
N
Motor rated current
Overload Protection
Service Factor
o
GBAS
Motor Current
Software Version
Line Voltage
Line Power
Elapsed time
Fault history Buffer
Password
E2PROM writting
Parameter Block Selector
M
v
V
w
E
e
K
W
G
f
GADV
GALL
GCAL
100-500
F,G ,H , ... ,X
m
40-120
0, N1, N2, N3,C1,C2
100-130
Calibration
parameters
e0, e1, e2, e3
1
2
Status
Shown automatically ON, STOP, LOCK, PULS, ...
(see page 4-4)
C / V
+
4-2
Line Power Factor
PF