Parameter
Parameter
Function
Read/Write
Range
Comments
number
name
(R/W)
0
Status
Soft starter status
R/-
0 - 14
0: ON
1: STOP
2: LOCK
3: Alarm (errors)
4: PULS
5: RAMP
6: FULL
7: SAVE
8: SOFT
9: DCBK
10: FULL (override)
11: Not used
12: INCH
13: TACH
14: PUMP
1
M
Motor current
R/-
(%N or Amps, depending on UF parameter)
2
N
Nominal motor current (% Unit current)
R/W
40-120
3
L
Limit current (% In)
R/W
100-700
4
T
Starting torque (% DOL torque)
R/W
10-90
5
a
Acceleration ramp time (sec)
R/W
1-99
6
d
Deceleration ramp time (sec)
R/W
1-120
7
p
Kick start time (msec)
R/W
0-999
8
b
DC brake time (sec)
R/W
0-99
9
I
DC brake current (% In)
R/W
50-250
10
S
Soft stop control
R/W
0-3
0: OFF
1: ON
2: I3
3: I4
11
C
Pump control
R/W
0-3
0: OFF
1: ON
2: I3
3: I4
12
P
Kick start control
R/W
0-3
0: OFF
1: ON
2: I3
3: I4
13
F
Override
R/W
0-3
0: OFF
1: ON
2: I3
3: I4
14
B
DC brake control
R/W
0-6
0: OFF
1: ON
2: I3
3: I4
4: PON
5: PI3
6:PI4
15
LK
Lockout (min.)
R/W
0-45
16
o
Overload trip curve
R/W
0-5
0: OFF
1: N1
2: N2
3: N3
4: C1
5: C2
17
internal use
18
W
Write EEPROM
-/W
1
19
R
Read EEPROM
-/W
1
20
-
internal use
21
v
Software version
R/-
xxx
vxxx
22
-
internal use
23
-
internal use
6. Appendix
6-2-5. List of parameters that can be controlled by the serial interface
6-9