SEQUENCE of OPERATION
PAGE
22
ENGLISH
Defrost
Indoor Unit
Temperature Sensors
Communication
Outdoor Unit
Temperature Sensors
When the system initiates a call for defrost, the indoor fan
motor stops. The indoor unit display will not change.
The system will cycle through the defrost operation.Any
indoor unit malfunctions will be ignored until the compressor
restarts and has been operating for 30 seconds.At the
conclusion of the defrost cycle, the indoor fan will enter the
cold air proof operationand heating resumes.
To enter the heat mode, point the infrared remote controller
at the unit and press the power button, then press the HEAT
mode button if not already set.
The louver stepper motor to open the louver to a stationary
position.
The indoor and outdoor units main boards communicate via
the wire connected to terminal 3 of each unit.A splice or break
in this wire will cause a communication error.
Upon a request for heat, the PCB applies power to the 4-way
valve,outdoor fan motor, and compressor.Depending on
system cycling, there may be up to a 3 minute wait period
before the compressor and outdoor fan start.
NOTE: Do not measure compressor voltages , damage to the
meter may result.
If the room temperature is above the set temperature,yet lower
than 2°F above the set temperature, the system will adjust the
running frequency of the compressor automatically.
The PCB also controls the position of the
EEV (Electronic Expansion Valve)
to regulate the flow of refrigerant to the indoor unit evaporator
coil.
Four sensors provide temperature information to the main board
for control of the system during heat mode.
The ambient sensor provides the temperature of the air drawn
into the evaporator coil.
The defrost temperature sensor provides the temperature
sensed at the output of the evaporator coil.
The suction line sensor provides the temperature
sensed at the incoming suction line pipe.
The PCB will illuminate the display, indicating the temperature
and current status.
The louver opens to the lowest downward position, then the
fan motor starts after the coil has warmed to a sufficient
temperature (cold air proof operation). The PCB sends the
motor information to monitor the speed if in the AUTO mode,
or returns the motor to the fixed speed set previously.
The room (ambient) and coil sensors are used to maintain
the system at the temperature desired. The resistance values
of the sensors can be verified using the temperature-to-
resistance charts found in this manual.
Call to Terminate Heating
The compressor discharge sensor provides the temperature
sensed at the discharge pipe of the compressor.
The system will call to terminate heating when the temperature
is equal to or higher than 2°F above the set temperature.
The PCB
will de-energize
the compressor. The outdoor fan will run for 60 seconds
before stopping, and the 4-way valve will de-energize 2 minutes
after the compressor stops.
To stop heat mode, press the power button to turn the system
Dry Mode
Overview
(Tr = room temperature Ts = set temperature)
When Tr > Ts + 4°F, the compressor will turn on and the indoor
fan will operate at the set speed.
high dry frequency for 10 minutes, then at the HIGH DRY and
LOW DRY mode for 6 minutes. The indoor fan will operate at
LOW speed. When Tr < Ts, the outdoor unit will stop, and the
indoor fan will stop for 3 minutes, then operate at the LOW
speed option.
Automatic fan speed:
When Tr >= Ts + 9°F, HIGH speed
When Tr < Ts + 3.6°F, Light speed
controller.
If the outdoor fan is stopped, the indoor fan will pause for 3
minutes.If the outdoor fan is stopped for more than3 minutes,
and the compressor is still operating, the sindoor fan will change
to low speed mode.
Dry mode helps remove excess moisture from the room
during periods of high humidity.
Summary of Contents for ASYW09CRAWA
Page 2: ...This page intentionally left blank...
Page 6: ...INTRODUCTION PAGE 6...
Page 26: ...INSTALLATION PAGE 42 ENGLISH This page intentionally left blank...
Page 58: ...REFERENCE INFORMATION PAGE 58 ENGLISH Outdoor Board Schematic 9 12K...
Page 59: ...REFERENCE INFORMATION PAGE 59 Outdoor Board Schematic Outdoor Board Schematic ENGLISH...
Page 63: ...REFERENCE INFORMATION PAGE 63 ENGLISH Indoor Board Schematic 09 12K...