ATS125x 4-Door DGP Installation Manual
11
Table 5: RAS address and reader function
IN IN OUT
OUT
Door
1 1 5 9 13
Door
2 2 6 10 14
Door
3 3 7 11 15
Door
4 4 8 12 16
Outputs
The 4-door DGP has one output available as a switched power output (external siren
output). There are also four onboard unlock relays available, one for every door (K1
to K4).
A 4-door DGP can address 48 outputs in total using macro logic.
Output controllers are used to expand the number of outputs on a DGP. Each output
controller expands the outputs by eight. Output and zone numbers are always the
same as the first 16 zone numbers on the DGP to which they are connected.
Outputs devices
ATS1810:
4-way relay card allows the use of output numbers 5 to 8 of the outputs
allocated to the DGP address. For example, DGP 1 uses unlock relay 17, 18, 19, and 20
for opening doors, and outputs 21 to 24 are available on the relay card.
Note:
this card cannot be used together with ATS1811/ATS1820 clocked output
cards.
ATS1811:
8-way relay cards allow use of output numbers 5 to 48 of the outputs
allocated to the DGP address. For example, DGP 1 uses unlock relay 17, 18, 19, and 20
for opening doors and outputs 21 to 63 are available on the relay cards.
ATS1820:
16-way open collector card. This is the same as ATS1811.
The 4-door DGP can activate outputs 33 to 63 only by utilizing macro logic.
When using more than two ATS1811s or ATS1820s, use a separate power supply.
ATS125x default zone and relay settings
Table 6: ATS125x defaults
Door 1
Door 2
Door 3
Door 4
Door
contact
1 3 5 7
Request-to-exit
zone
2 4 6 8
DOTL
1 3 5 7
Door
relay
K1 K2 K3 K4