 Point 

ID 

DGP

I

NTRODUCTION

 

The ATS1290 is an interface between the ATS LAN-bus and 
a Point ID bus (GE proprietary Point ID protocol). The PID-
DGP provides two-wire bi-directional communications with 
up to 32 individually addressed PID-devices. The ATS1290 
is intended to be sitting on the LAN of any existing 
configuration of ATS products to expand the system with 
addressable devices. A maximum of up to 15 ATS1290 
DGPs can be connected to the LAN. 

M

OUNTING THE UNIT

 

Mount the ATS1290 PCB in any existing ATS series 
enclosure that supports the BB format. 

C

ONNECTIONS 

CON1 (

SEE FIG 

1, 



 AND 

‘

COMMS

   12 VDC power supply. It is recommended that 

where the distance between an ATS1290 and the 
nearest device is more than 100 meters, a 
separate power supply be used. Refer to the 
Remote DGP section. When using an external 
power supply, use a fused power output (1 A 
fast). 

COMMS

   Positive and negative data connection of the 

system databus. Units can be up to 1.5 km from 
the ATS control panel, depending on the cable 
used. See the ATS control panel installation guide 
for details. 

TAMP

 

The PCB tamper switch is connected in parallel to 
the external tamper connection. Tamper switch 
requires normally open contacts. 
Note: Depending on the type of housing used, 
you can use the PCB tamper or connect an 
external tamper. 

CON10 (

SEE FIG 

1, 

’

Earth connection. Connect the shield of the ATS COMMS 
cable. At the other end of the cable the shielding must be 
connected to one system earth. See the ATS control panel 
installation guide. This is not applicable for the possible 
shielding of the PID-bus. 

DGP 

DIPSWITCH SETTINGS 

(

SEE FIG 

1, 

—

 

FIG 

2) 

ADDR

  DIP switches 1 to 4 are used to identify the DGP 

number to the ATS control panel. Select the required DGP 
number and set the Address DIP switch as indicated in 
figure 2. 

LED

(

SEE FIG 

1, 

•

RX

 

LED flashes to indicate polling data is being 

received on the system databus from the ATS control panel. 
If the LED does not flash, the control panel is not operational 
or the databus is faulty (usually cabling). 

TX

 

LED flashes to indicate the DGP is replying to 

polling from the ATS control panel. If the RX LED flashes 
but the TX LED does not, it indicates that the DGP is not 
programmed to be polled in the control panel or that it is 
addressed incorrectly. 

I

NSTALLING 

P

OINT 

ID 

DEVICES

 

C

ONNECTIONS 

CON2 (

SEE FIG 

1, 



 

FIG 

3) 

PID

 

Connection to all Point ID devices. Requires one + 

and one – terminal to be connected. This will provide power 
supply and data. 

Devices provide for two bus terminals (see 

‘

) or only one 

terminal (see 



 & 



). The bus loop does not need special 

termination. 

C

ABLE 

T

OPOLOGY 

PID – BUS (

SEE FIG 

4

)

 

In principle the bus-topology is free.  
Shown are several topologies (see figure 4): 

• 

Lumped

 (all PID-devices at the end) 

Distributed 

(all PID-devices distributed across the line) 

• 

Star

 (all devices with own branches to a star point) 

• 

Remote

 DGP (A DGP positioned remote from a 

power-supply)

 

In practice there will be a mix of topologies. 
 

Cable types

:  

WN108

, Unshielded, 8 core cable  

WS108

, Shielded, 8 core cable + shield 

WCAT54

: 4 pairs of FTP category 5 cable 

These cables all have a core with a gauge of AWG24, 
the diameter is 0.52mm and the Area is 0.22mm

².  

Preferred cable is the WCAT54 folowed by the WN108 
and finally the WS108. In principle, use cables with as 
low resistance and capacitance as possible.  
If a shielded cable is used for the PID-bus, this must 

not

 

be connected to either earth, PID- or PID+. If connected, 
it would result in additional capacity.  
The tables below show the maximum cable lengths in 
metres for different cable types. The number of devices 
and device load are taken into account. Check the device-
manuals for the “Unit Load”. 1 Unit load corresponds to 
300uA typical current. 

Note

: The absolute minimum working voltage for the PID-

bus is 9.5VDC (measured on COMMS 12VDC power supply 
of the DGP). This is 1VDC under the low battery level of 
10.5VDC.  
The 9.5VDC is the minimum voltage for the following 
situations: 

1.  All PID-bus powered PID-devices (Typical situation) 
2.  External powered PID-devices (Retrofit situation) 

1. PID-devices powered out of the PID-bus 

Combine 4 wires for PID+ and 4 for PID-.. 

Lumped and Distributed (distance X) 

# Dev 

Unit Load 

WN 108 

WS 108 

WCAT54 

32  1 

1600 1200 1600 

16  16  200 200 200 
16  32  100 100 100 
 

Star (distance Q) 

# Dev 

Unit Load 

WN 108 

WS 108 

WCAT54 

32  1  200 160 200 
16  16  150 120 150 
16 32 100 75 100 

Note:

 By using a WN104 instead of a WN108 (cores 

reduced by half), the cable lengths will be reduced by 50%. 
For twisted pair cables, combine the pairs instead of 
combining one core of the pair 
 

D+ 

D- 

Ti 

Tc

 

Summary of Contents for ATS1290

Page 1: ...curity B V 1052285 All rights reserved 02 2005 Fig 2 Fig 1 Fig 3 DGP Lumped X Y Control Panel DGP Distributed X Z Control Panel Star DGP Q Control Panel Remote DGP DGP R Control Panel Fig 4 ATS1290 Po...

Page 2: ...17 0 PIR T0 Input No 17 0 Normal 0 Exit 3 Device Settings 0 Exit Menu 17 0 PIR T0 Input No 17 0 Loc1 0 Value Or 17 0 1 00000000 Bits 4 Reset Settings 0 Exit Menu 17 0 PIR T0 Input No 17 0 Reset Y N Y...

Page 3: ...t the DGP is not programmed to be polled in the control panel or that it is addressed incorrectly INSTALLING POINT ID DEVICES CONNECTIONS CON2 SEE FIG 1 FIG 3 PID Connection to all Point ID devices Re...

Page 4: ...rol one walk test LED of one PID device It is also possible to control all walk test LEDs of all AD111 by one output The only requirement is that the output needs to be within the DGP range Program th...

Page 5: ...n is required before the settings are reset to factory defaults When the settings are unknown all locations will be set to 0 5 Learn mode Equal to shortening the JP2 jumper for a few seconds Will ente...

Page 6: ...centrale ATS Si la LED RX clignote alors que la LED TX ne clignote pas cela signifie que le DGP n est pas programm pour tre scrut dans la centrale ou que son adresse est incorrecte INSTALLATION DE PE...

Page 7: ...Adresse Adresse d tecteur interne ex 750 AD Param trage du micro interrupteur sur le d tecteur 17 0 00000000 18 1 10000000 19 2 01000000 4 me DGP Adresse Adresse d tecteur interne ex 750 AD Param tra...

Page 8: ...ans la port e d tecteur Appuyez sur 0 puis ENTER ENTREE pour quitter 3 Device settings Param tres du d tecteur Fournit une liste de s lection comme pour le menu 2 Appuyez sur le num ro de zone puis EN...

Page 9: ...D de point CON2 9 9 13 2 V donn es et impulsions suppl mentaires Alimentation de sortie ID de point maximale 13 2 V 5 154 mA 512 unit s de charge max Dimensions 80 mm x 90 mm Poids 160 gr Temp rature...

Page 10: ...isor Master controlepaneel Indien de RX LED knippert maar de TX LED niet is de DI niet geprogrammeerd op het controlepaneel voor pollen of onjuist geadresseerd POINT ID MODULES INSTALLEREN AANSLUITING...

Page 11: ...67 2 01000000 15 e DI Adres Module bijv 750 AD Adres Instelling DIP schakelaar op interne module 241 0 00000000 242 1 10000000 243 2 01000000 Functionaliteit combineren op n uitgang Bij bepaalde toep...

Page 12: ...gevolgd door ENTER om het configuratiemenu te openen U kunt nu alle configuratielocaties invoeren Met de toets MENU kunt u heen en weer schakelen tussen waarde en bit presentatie Bij waarde presentati...

Page 13: ...sluitspanning CON2 9 9 13 2V aanvullende data pulses Max Point ID uitgangsstroom bij 13 2V 5 154mA max 512 eenh van belasting Afmetingen 80 mm x 90 mm Gewicht 160 gr Temperatuur 10 C tot 50 C Relatiev...

Page 14: ...generalmente si tratta di un problema di cablaggio TX Il LED lampeggia per indicare la risposta del concentratore all interrogazione inviata dalla centrale ATS Se il LED RX lampeggia ma il LED TX no...

Page 15: ...D Impostazione interruttore DIP sul dispositivo interno 65 0 00000000 66 1 10000000 67 2 01000000 Indirizzo 15 concentratore Indirizzo dispositivo interno es 750 AD Impostazione interruttore DIP sul d...

Page 16: ...Qui possibile immettere tutte le posizioni di configurazione Utilizzare il tasto MENU per alternare la visualizzazione in valore e bit Se si utilizza la visualizzazione in valore immettere un valore d...

Page 17: ...Alimentazione Point ID CON2 9 9 13 2V impulsi dati aggiuntivi Corrente massima di uscita Point ID a 13 2 V 5 154 mA carico unitario massimo 512 Dimensioni 80 x 90 mm Peso 160 g Temperatura Da 10 C a 5...

Page 18: ...3 PID Tilslutning til alle Point ID enheder Kr ver at der tilsluttes en plustermininal og en minusterminal Dette sikrer str mforsyning og muligg r datatransmission Enheder indeholder enten to bustermi...

Page 19: ...1 enheder via en enkelt udgang Den eneste betingelse for at kunne g re dette er at udgangen er inden for PID DGP ens r kkevidde Programm r ATS style output for alle relevante PID enheder til n specifi...

Page 20: ...Du skal bekr fte handlingen f r indstillingerne nulstilles til standardindstillingerne N r indstillingerne er ukendte nulstilles alle placeringer 5 Learn mode indl sningstilstand Svarer til at kortsl...

Page 21: ...u keskuslaitteessa pollattavaksi tai sen osoite on m ritetty v rin OSOITTEELLISTEN LAITTEIDEN ASENTAMINEN LIIT NN T CON2 KATSO KUVA 1 JA KUVA 3 PID Liit nt kaikkiin osoitteellisiin laitteisiin Kytkemi...

Page 22: ...rkkivalojen ottamista k ytt n ja poistamista k yt st Normaalitapauksessa on liitetty yksi k velytestin merkkivalon k ytt n ottava k yt st poistava l ht suoraan keskuslaitteesta PID laitteeseen Kukin l...

Page 23: ...l pi kaikki asetukset mink j lkeen muutokset tallennetaan 4 Palauta oletukset Reset settings N ytt samanlaisen valintalistan kuin valikko 2 Palauta haluamasi laitteen asetukset tehdasasetuksiin n pp...

Page 24: ......

Reviews: