background image

Summary of Contents for AZ75H12EACM1 and

Page 1: ...llation Instruc_tions Electrical Supply 1 13 Installing the Zoneline 4 21 Preparation 0 Servicing 22 Troubleshooting Tips 23 Normal Operating Sounds 24 Consumer Support Consumer Support Back Cover Pro...

Page 2: ...amaged A damaged power supply cord must be replaced with a new power supply cord obtained from the mamffacturer and not repaired Do not use a cord that shows cracks or abrasion damage along its length...

Page 3: ...e _ shipping screw The fi_cto U settings will be in the DOWN position NOTE The owner is responsible tot setting the appropriate dip switches and connecting temdnals TL1 C Temp Limit1 Cool TL2 C Temp L...

Page 4: ...D DOWN DOWN L CONST FAN Constant ONFan OccupancySensor _ _ en this switch is enabled UP it allows tile trait to utilize an infl ared motion sensor and a door switch tot occui ancy detection This timt...

Page 5: ...ontrolled by switches 1 6 on the top block TL1 C Temp Limit1 Cool TL2 C Temp Limit2 Cool TL3 C Temp Limit3 Cool aBBBBBI DOWN aaaaaal DOWN TL1 H Temp Limit 1 Heat TL2 H Temp Limit2 Heat TL3 H Temp Limi...

Page 6: ...ng tile appropriate dip switches and connecting temfinals CAUTION hnproper CDC Mring may damage tile Zoneline Routewires electronics or cause erratic Zoneline operation through wire No common busing i...

Page 7: ...nd enei _ry i anagei ent ol ei ations CentralDesk Control 4lien connected tile unit lock out is released and it can be turned ON or OFF with a switch located at the entral Desk ontrol A separate wire...

Page 8: ...e vent push the vent lever handle down pull it fin ward and lock it up in place Toopen the vent push the vent lever handle down push it back and lock it up in place 0 Ventcontrol pushleverdown andpull...

Page 9: ...lters To maintain optimum performance change the filter at least every30 days The most important thing ou can do to Toremove maintain the Zoneline is to change the filter at and replace least eve_w 30...

Page 10: ...ed electrician Follow the National Electrical Code NEC and or local codes and ordinances For personal safety this Zoneline unit and case must be properly grounded Protective devices fuses or circuit b...

Page 11: ...ection and the amperage of the branch drcuit See the PO_ ER CONNECTION CHART on page 13 to select the ai i ropriate kit Power supply kit M1 wirin including installation of the receptacle must be in ac...

Page 12: ...Code Plugging this unit into a building mounted exposed receptacle is not permitted b code These models must be installed using the ai propriate GE power suppl kit tot tile branch circuit amperage and...

Page 13: ...The white lead d the power supply kit should be com_ected to neutral Cmmect the green lead of the power supply kit m the power supply and branch circuit grotmd 3 Phase 253 277 VAC IIIw _onrwcii g the...

Page 14: ...VWP8 8 D x 193A Wx 32 H RAVWP12 12 D x 193 4 1N x 32 H RAVWP15 15 D x 193 4 1N x 32 H Cutout Dimensions 28 M x 48 H Access Panel with OR Return Air Grille RAVRG1 22i z I Cutout Dimensions 203 8 VVx 20...

Page 15: ...n1 Accesspanelwith returnair grille Option2 Returnair grille 3 _ _ rain Side View Rigid _ ductwork Flexibleor _ rigid duct Air discbarge_ _1 Wall plenum a divider _ _ l I F FHterbracket 7 p to t e f o...

Page 16: ...endsand tees Flexduct roaybe used for transitions only Outsidewall I I I I I D 230 208VAC wall receptacle or conduit for direct connection Reference Dimensions A Them ostat cable 9 long B Power cord 6...

Page 17: ...oose the option that best suits w ur installation requirements Follow the Installation Instructions i rovided with the return air grille accessory for installation details NOTE Use only one filter in...

Page 18: ...enum RAVWP6 6 D x 19 VV x 32 14 RAVWP8 8 D x 19 VV x 32 14 RAVWP12 12 D x 19 VV x 32 14 Case RAVWP15 15 D x 19 Wx 32 14 BUILD AND INSTALL THE ZONELINE BASE PLATFORM 1 Construct a 23V rain x 23 rain sq...

Page 19: ...on top _ff the case accepts standard 10 duct Pull all duct tight Extra duct slack can greatly increase static pressure CAUTION Flex duct can collapse mad cause airflow restrictions Do not use flex du...

Page 20: ...INSTALLED THROUGH FRONT OF CASE 1 Slide tile back oI tile unit into tile case Push tile unit all of tile way into tile case until it stops NOTE Either of tile case sides may be removed to enable tile...

Page 21: ...ft for AW6 24 AWG AmericanWire Gauge 2 Make power connections to tile trait No rE See tile ELECTRICALREOUIREMENTS md DIRECT CONNECTAPPLICATIONS secdons as appropriate ot this inanual for proper conne...

Page 22: ...ING kWARNING Before ser icing switch power off at the service panel and lock the area to prevent power fl om being switched on accidentally When the area cammt be locked securely fasten a prominent wa...

Page 23: ...restrictive tor proper perfinmance Consult your salespei_on tor assistance Change the filmr at least every 30 days See the Care and Cleaning Air Filter section When the Zoneline is fii_t turned oil v...

Page 24: ...cycle up This will cause the tim to cycle on and off with the COIlll I eSSOI roll Ill ly also hear a thn noise stop and staY _t Ym may notice a tew minutes delay in starting if w_u ti T to restart ti...

Page 25: ..._ Ct t here Please place in envelope and mail to General Electric Company Warranty Registration Department P O Box 32150 Louisville KY 40232 2150 25...

Page 26: ...ou did not get a registration card with your product detach and return the form below to ensure that your product is registered or register online at ge com _ _ Cut ll _r _ Consumer Product Ownership...

Page 27: ...for providing adequate electrical comlecth_g facilities In commercial locations labor necessary to move the unit to a location where it is accessible for service by ml hldJviduaJ teclnficimL Failure o...

Page 28: ...ebsim today For tile heating impaired please call 800 TDD GEAC 800 833 4322 PartsandAccessories ge com Individuals qualified m se_ ice their own appliances can have parts or accessories sent directly...