CHAPTER 4: INTERFACES
FRONT PANEL INTERFACE
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
4-21
4
The letters T, S, B, R, and X next to a controllable element have the following meaning. An example (TSB) is shown in the
next figure.
•
T — The element is "tagged." Local and remote control of the device are inhibited, both open and close. Tripping is
unaffected unless additional logic has been configured.
•
S — The position indication of the device is substituted with a manually entered value
•
B — Blocking open/close command is bypassed
•
R — Autoreclose is enabled and not blocked
•
X — The device is out-of-service and control is not available
Single-line diagram example
The following example outlines how to create a circuit breaker diagram, then how to close the second circuit breaker. The
figure shows six switches (SW, M), two breakers (CB), feeder (arrow), and ground (lined arrow).
Figure 4-25: Single-line diagram of open circuit breakers
Under
Settings > System Setup > Switches
and
Breakers
, enable and name the six switches and two breakers. Switch 6,
M568G, has the A/3 Pole Opened setting on.