CHAPTER 5: SETTINGS
PRODUCT SETUP
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-25
5
In addition to supporting syslog, a B30 with CyberSentry also saves the security events in two local security files, these
being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in
the EnerVista software under
Maintenance > Retrieve File
. Depending on the level of criticality/severity, a syslog server or
a reporting tool gathering information from a syslog server can produce reports, charts, and so on. All severity levels are
per RFC 5424.
Table 5-6: CyberSentry system events recorded
5.3.2 Display properties
SETTINGS
PRODUCT SETUP
DISPLAY PROPERTIES
10
Clear Energy command (not applicable to all UR products)
11
Clear Unauthorized Access command
12
Clear Teleprotection Counters command (not applicable to all UR products)
13
Clear All Relay Records command
14
Role Log in
15
Role Log off
Event
Severity
Description
FAILED_AUTH, ORIGIN, TIMESTAMP
Warning (4)
A failed authentication with origin information (username and IP:MAC
address), a time stamp in UTC time when it occurred
AUTH_LOCKOUT, ORIGIN, TIMESTAMP Error (3)
An authentication lockout has occurred because of too many failed
authentication attempts
FIRMWARE_UPGD, ORIGIN,
TIMESTAMP
Warning (4)
Indicates that a change of firmware has occurred
FIRMWARE_LOCK, ORIGIN,
TIMESTAMP
Critical (1)
An attempt was made to change firmware while the firmware lock was
enabled
SETTING_CHG, ORIGIN, TIMESTAMP
Notice (5)
Indicates setting change(s)
SETTING_LOCK, ORIGIN, TIMESTAMP Critical (1)
An attempt was made to change settings while the settings lock was enabled
LOGIN, ORIGIN, TIMESTAMP
Warning (4)
Indicates when a certain role logged in
LOGOUT, ORIGIN, TIMESTAMP
Notice (5)
Indicates when a certain role logged out or timed out
CLEAR_OSCILLOGRAPHY
Notice (5)
Clear oscillography command was issued
CLEAR_DATA_LOGGER
Notice (5)
Clear data logger command was issued
CLEAR_DEMAND_RECS
Notice (5)
Clear demand records command was issued
CLEAR_ENERGY
Notice (5)
Clear energy command was issued
RESET_UNAUTH_ACCESS
Warning (4)
Reset Unauthorized access command was issued
CLEAR_TELEPROTECTION_CNT
Notice (5)
Clear teleprotection counters command was issued
CLEAR_ALL_RECS
Warning (4)
Clear all records command was issued
DISPLAY
PROPERTIES
LANGUAGE:
English
Range:
English; English, French; English, Russian; English,
Chinese; English, German (examples; depends on order code)
Visible when language other than English purchased
FLASH MESSAGE
TIME: 1.0 s
Range: 0.5 to 10.0 s in steps of 0.1
DEFAULT MESSAGE
TIMEOUT: 300 s
Range: 10 to 900 s in steps of 1
DEFAULT MESSAGE
INTENSITY: 25 %
Range: 25%, 50%, 75%, 100%
Visible when a VFD is installed
SCREEN SAVER
FEATURE: Disabled
Range: Disabled, Enabled
Visible when an LCD is installed
Enumeration Description
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...