CHAPTER 5: SETTINGS
PRODUCT SETUP
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-57
5
Figure 5-18: IEC 61850 protocol panel in EnerVista software
The IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and click
an option on the left to display its panel on the right. The following figure shows an example for Server Configuration. The
SETTING
column contains the names of the settings, and the
PARAMETER
column is used to enter the settings. Hovering
the mouse over a setting name displays a tool-tip showing the 61850 information model name of the setting or its location
in SCL files.
Figure 5-19: IEC 61850 panel
Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the B30.
This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those
that are mapped into the IEC 61850 information model (that is, the "public" sections) and those that are not in the model
(that is, the "private" section). The UR EnerVista Setup software imports all of these settings into the current session, not just
those in the IEC 61850 window. To avoid loss of any unsaved setting changes made in other panels during the current
session, all other panels for the B30 must be closed before the IEC 61850 panel can be opened, and the software prompts
for this when applicable. Panels for other devices can be open concurrently to facilitate parameter coordination.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...