5-96
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Figure 5-44: IEC 61850 GGIO1 panel
GGIO1 INDICATION 1
Range: any FlexLogic operand
Default: OFF
This setting selects the FlexLogic operand whose value is mapped into the IEC 61850 data attribute
<LDName>/GGIO1.Ind001.stVal. See the FlexLogic section in this chapter for a list of FlexLogic operands.
GGIO1 INDICATION 2
Range: any FlexLogic operand
Default: OFF
Selects the FlexLogic operand mapped to <LDName>/GGIO1.Ind002.stVal, and so on.
GGIO2
Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by
Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here.
Navigate to
Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO2
to access the settings that
configure the IEC 61850 protocol interface for Virtual Input commands.
Figure 5-45: GGIO2 panel