CHAPTER 5: SETTINGS
SYSTEM SETUP
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-147
5
This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
Figure 5-68: Example of use of sources
5.5.4 Breakers
SETTINGS
SYSTEM SETUP
BREAKERS
BREAKER 1(6)
Y LV
D HV
AUX
SRC 1
SRC 2
SRC 3
Phase CT
M1
F1+F5
None
Ground CT
M1
None
None
Phase VT
M5
None
None
Aux VT
None
None
U1
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
BREAKER 1 TAGGING:
Disabled
Range: Disabled, Enabled