CHAPTER 5: SETTINGS
SYSTEM SETUP
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-155
5
SWITCH 1 OPEN
— This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch 1
open command.
SWITCH 1 BLK OPEN
— This setting selects an operand that prevents initiation of the disconnect switch 1 command. This
setting can be used to block the disconnect switch from opening, for instance when switchyard monitoring indicates that
current exceeding the switch's interrupting rating can be flowing through the switch.
SWITCH 1 CLOSE
— This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch
1 close command.
SWITCH 1 BLK CLOSE
— This setting selects an operand that prevents initiation of disconnect switch 1 close commands. This
setting can be used to block the disconnect switch from closing, for instance to prevent closing into a closed ground
switch.
SWTCH 1
Φ
A/3P CLSD
— This setting selects an operand, usually a contact input connected to a disconnect switch auxiliary
position tracking mechanism. This input is for a normally-open 89/a status input that creates a logic 1 when the
disconnect switch is closed. If the
SWITCH 1 MODE
setting is selected as “3-Pole,” this setting selects a single 89/a input as
the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole,” the input
mentioned is used to track phase A and the
SWITCH 1
Φ
B
and
SWITCH 1
Φ
C
settings select operands to track phases B and
C, respectively.
SWTCH 1
Φ
A/3P OPND
— This setting selects an operand, usually a contact input, that is for a normally-closed 89/b status
input that creates a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available, then an
inverted 89/a status signal can be used.
SWITCH 1
Φ
B CLOSED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B closed position as outlined for phase A.
SWITCH 1
Φ
B OPENED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase B opened position as outlined for phase A.
SWITCH 1
Φ
C CLOSED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C closed position as outlined for phase A.
SWITCH 1
Φ
C OPENED
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
pole, this input is used to track the disconnect switch phase C opened position as outlined for phase A.
SWITCH 1 PUSH BUTTON CONTROL
— Set to "Enable" to allow front panel pushbutton open/close control operations.
SWITCH 1 TAGGING
— Set to "Enable" to allow the graphical front panel to tag switch 1. When tagged, the following
operations are disabled:
•
Pushbutton Open/Close
•
IEC 61850 Open/Close
•
Open command initiated by
SWITCH 1 OPEN
setting
•
Close command initiated by
SWITCH 1 CLOSE
setting
SWITCH 1 SUBSTITUTN
— Set to "Enable" to allow the graphical front panel to substitute switch 1 status. When substituted,
switch 1 control open/close status is forced to the substituted value.
SWITCH 1 BYPASS
—Set to "Enable" to allow the graphical front panel to bypass switch 1 interlocking. When asserted,
SWITCH 1 BLK OPEN
and
SWITCH 1 BLK CLOSE
settings are bypassed.
SWITCH 1 OPEN SEAL-IN
— This setting specifies the seal-in time of the open command due to an operator-initiated manual
open command to the disconnect switch.
SWITCH 1 CLOSE SEAL-IN
— This setting specifies the seal-in time of the close command due to an operator-initiated manual
close command to the disconnect switch.
SWITCH 1 TOPERATE
— This setting specifies the required interval to overcome transient disagreement between the 89/a
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
FlexLogic operand is asserted for alarm or blocking purposes.
SWITCH 1 ALARM DELAY
— This setting specifies the delay interval during which a disagreement of status among the pole
position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the poles.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...