background image

Page 9

For battery charger systems with capacitor filtered outputs, the Battery Alarm requires a
choke of 

2mH to be fitted at the output of the battery charger to ensure correct operation of

the high impedance alarm (see Figure 1).

In normal operation, the non-urgent (earth fault or high volts cut-off) relay is de-energised and
the urgent relay is energised, thus providing a ‘fail to safety’ feature.

If the supply voltage falls below 66% nominal for longer than 50 milliseconds, an
instantaneous urgent alarm is given. When the supply voltage returns to above 66% nominal
a ‘power on reset’ occurs after a time delay of 1 second.

Operation

The Battery Alarm derives its power supply from the battery being monitored. The current
consumption is approximately 20mA. Four monitoring functions are provided:

A. Earth fault alarm (positive and negative).

B. Over voltage alarm.

C. Under voltage alarm.

D. High battery impedance alarm.

A common configuration for alarm relay outputs is routing functions B, C and D via a timer
circuit to the urgent relay.

Six LED indicators are provided for diagnostic purposes and under normal healthy conditions
only the one monitoring the power supply is lit.

The LEDs for all four functions listed above will light instantaneously when a fault is detected
and the urgent and non-urgent alarm relays will trip after their preset time delays.

Commissioning

Battery Alarms are available calibrated for other battery voltages between 24V and 220V.
They are designed for flush panel mounting in a cut-out measuring 92mm square (+0.8, –0),
and secured in position with the clamps provided. Before connecting up, ensure that the unit
supplied is suitably rated for the battery installation to be monitored, otherwise damage
could be sustained. Connect the + and – terminals and also connect the E terminal to earth.
Connect the output contacts to the telemetry or other alarm annunciators as required.

After carefully removing the small access window, the front-mounted potentiometers can be
adjusted as follows:

1. High Impedance

Rotate this control anticlockwise until the associated LED is lit, then slowly rotate
clockwise until the LED is just extinguished. This gives maximum sensitivity. Further
clockwise rotation increases the trip impedance.

2. Over Voltage – preset at factory.*

3. Under Voltage – preset at factory.*

* A limited amount of adjustment is possible to suit a particular installation but an
injection test is preferred (apply to factory for details).

Summary of Contents for BA300

Page 1: ...GE Grid Solutions BA300 Battery Alarm Commissioning Instructions For use with Substation and Telecontrol Batteries Publication reference BA300 EN CI GE ...

Page 2: ......

Page 3: ...he case 2 Handle the module by its front plate frame or edges of the printed circuit board Avoid touching the electronic components printed circuit track or connectors 3 Do not pass the module to any person without first ensuring that you are both at the same electrostatic potential Shaking hands achieves equipotential 4 Place the module on an antistatic surface or on a conducting surface which is...

Page 4: ...ent of the North American term ground Installing Commissioning and Servicing Equipment connections Personnel undertaking installation commissioning or servicing work on this equipment should be aware of the correct working procedures to ensure safety The product documentation should be consulted before installing commissioning or servicing the equipment Terminals exposed during installation commis...

Page 5: ... maximum rating of the external protective fuse for this equipment is 2A Red Spot type or equivalent Insulation class IEC 61010 1 1990 A2 1995 This equipment requires a Class I protective safety earth EN 61010 1 1993 A2 1995 connection to ensure user Class I safety Installation IEC 61010 1 1990 A2 1995 Distribution level fixed Category Category III installation Equipment in Overvoltage EN 61010 1 ...

Page 6: ...rminal must be connected to earth If either the positive or negative of the battery is earthed the standard Battery Alarm 300 will indicate an earth fault alarm In the case when an earth relay is already fitted a Battery Alarm 300 model without earth fault is recommended Test Method for Battery Alarm The unit can be tested using the equipment shown in Figure 2 With this set up carry out the follow...

Page 7: ...delay 7 Timer Increase the voltage to a value above the over voltage trip point Note the time between the over voltage alarm LED coming on and the output relay alarm tripping 8 High Impedance Set the power supply voltage midway between the two voltage trip points Increase the series resistance 5 from zero until the high impedance LED comes on NB Reset the series resistance to zero 9 Earth Fault Po...

Page 8: ...pplication note Battery charger systems with an inductive output element only should have a suitable load connected such as a battery during commissioning and normal operation This is to avoid resonance of the output inductor with the system capacitance which may produce damaging high peak output voltages For use with inductor only filtered chargers a small standing drain will be required on the b...

Page 9: ...nly the one monitoring the power supply is lit The LEDs for all four functions listed above will light instantaneously when a fault is detected and the urgent and non urgent alarm relays will trip after their preset time delays Commissioning Battery Alarms are available calibrated for other battery voltages between 24V and 220V They are designed for flush panel mounting in a cut out measuring 92mm...

Page 10: ...etting 0 5 Earth leakage protection preset Trip level range 5kΩ to 90kΩ Accuracy of trip level 10 Hysteresis on trip level 5 Short circuit current 5mA High impedance alarm adjustable Setting range 0 1Ω 5 0Ω Accuracy of setting 0 05Ω Hysteresis on setting 0 05Ω Temperature Nominal range of use 20 60 C Reference temperature 23 C Temperature coefficient Voltage alarms 0 006 C Earth leakage alarm 0 06...

Page 11: ...ted If the front cover is removed to gain access to the adjustment potentiometers then appropriate ESD protection must be taken Low Voltage Directive 72 23 EEC Designed to EN61010 1 1993 safety requirements Timers Alarm time delay settings 1 2 4 8 16 32 64 128s other settings available on request Accuracy of setting 10 0 25s Output relays URGENT alarm relay 2 changeover contacts NON URGENT alarm r...

Page 12: ...is document is indicative only No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or disclosure to third parties without express written authority is strictly prohib...

Reviews: