Table 2: Travel Sensor Alignment
Rotary
Mounting
System
Stroke Direction
Magnet
Orientation
Valve
Position
Sensor Counts
Rotary
<60° Rotation
Clockwise or counter-
clockwise rotation
(0°)
Closed (0%)
0 +/- 1000
>60° Rotation
Clockwise with increas-
ing setpoint
(-45°)
Full Open
or
Full Closed
-8000 +/- 1500
or
+8000 +/- 1500
>60° Rotation
Counter Clockwise rota-
tion with increasing set-
point
(+45°)
Full Open
or
Full Closed
-8000 +/- 1500
or
+8000 +/- 1500
General Rule for
other configura-
tions
Any amount of rotation
Clockwise or counter-
clockwise
(0°)
50% Travel
(Mid-Stroke)
0 +/- 1000
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Masoneilan SVi1000 Positioner Quick Start Guide
=
|
25
c. Aligning the end of the magnet holder flush with the end of the mounting
bracket. Secure the magnet holder with two M4 set screws.
d. Sliding the V-Seal over the magnet holder. You can also check the magnet using
ValVue software by reading sensor counts and comparing them to Table
4. Secure the SVi1000 onto the mounting bracket using four M6 x 20 mm socket
head cap screws.
5. Ensure no interference exists with the position sensor protrusion.
Summary of Contents for BAKER HUGHES Masoneilan SVi 1000
Page 1: ...Masoneilan SVi 1000 Positioner Quick Start Guide Rev L BHGE Data Classification Public...
Page 8: ...This page intentionally left blank...
Page 18: ...This page intentionally left blank...
Page 38: ...This page intentionally left blank...
Page 56: ...This page intentionally left blank...
Page 86: ...This page intentionally left blank...
Page 87: ......