© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
80 |
=
BHGE
GE Oil & Gas
ES-761 Rev H
Page 8 of 13
Copyright 2018 as an unpublished trade secret. This document and all information herein is the property of Dresser LLC. It
is confidential and must not be made public or copied and is subject to return upon demand.
5.2
Operating Ranges
5.2.1
Temperature
-40
o
C to 85
o
C
5.2.2
Input Voltage
30 volts
5.2.3
Supply Pressure
100 psig
Clean instrument air and natural gas are the typical supply sources.
5.2.4
Current
4 to 20mA
5.3
Enclosure Type
NEMA
4X
Type
4X
IP66
5.4
Temperature Code
T4 Ta=85°C
5.5
Notes Related to Intrinsic Safety
1.
“Intrinsically safe when installed per ES-761”
2.
“Supply connection wiring rated for 5°C above maximum ambient temperature”
3.
Permanently mark the label for the protection type chosen. Once the type has been marked, it
cannot be changed.
4.
It must be ensured the thermal effect of the process temperature does not result in exceeding
the SVi1000 specified ambient temperature of -40
o
C to 85
o
C.