Autotune doesn’t complete
Feedback slipping, loose.
Rotary installation: magnet
assembly rotates using hands.
Reciprocating bracket: the turn-
buckle, rod-end, and take off
arm aren't secured.
Secure all set screws and
locking nuts.
Check reciprocating assem-
bling for binding during
operation.
In general, Autotune may
fail if the valve is too slow -
in this case manually tune.
Magnet far away from housing.
Rotary installation: the
face of the
magnet holder isn't flush with
the face of the mounting
bracket.
Cannot be recessed by more
than 1/8"
Loosen up the set screws
holding the magnet assem-
bly in the magnet holder
and pull the magnet so it is
flush with the mounting
bracket.
In general, Autotune may
fail if the valve is too slow -
in this case manually tune.
High friction, sticking, slipping.
The friction measured is
more than
30% of the spring force or the
valve is visibly jumping around
the
setpoint.
Run Autotune with
Aggres-
siveness settings of 2 or 4,
or, proceed to manually
tune the SVI FF ensuring the
Integral Gain (I) is set to a
minimum of 100.
In general, Autotune may
fail if the valve is too slow -
in this case manually tune.
Table 26 Troubleshooting Auto Tuning (Continued)
Problem
Presumed Cause
Remedy
See Section
Summary of Contents for Baker Hughes Masoneilan SVI FF
Page 12: ...This page intentionally left blank ...
Page 72: ...This page intentionally left blank ...
Page 82: ...This page intentionally left blank ...
Page 94: ...This page intentionally left blank ...
Page 108: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 224: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...
Page 230: ...This page intentionally left blank ...
Page 250: ...This page intentionally left blank ...
Page 262: ...This page intentionally left blank ...
Page 263: ......