Masoneilan SVI FF Instruction Manual
=
|
173
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
TEMPERATURE (1)
Current TEMPERATURE value.
Not writable for Standard Diagnostics version.
ALERT_POINT (2)
-45 to 85 85
TEMPERATURE
Value, above which the ALERT is set to True.
Not writable for Standard Diagnostics version.
DEADBAND (3)
0 - 2
2
TEMPERATURE
change, required to clear the ALERT
,
once it
was set to True.
Not writable for Standard Diagnostics version.
ALERT (4)
FALSE
True if the TEMPERATURE
has reached above
ALERT_POINT and have not come below
(ALERT_POINT-DEADBAND).
Not writable for Standard Diagnostics version.
HISTORIC ALERT (5)
True -
False
FALSE
True if ALERT is true.
Not changed if ALERT is false.
Not writable for Standard Diagnostics version.
ENABLE (6)
True -
False
TRUE
True - Enables the ALERT
to be reported according to the
configuration.
False - Disables ALERT
reporting.
Not writable for Standard Diagnostics version.
TEMPERATURE_LO_
ALERT (63)
Low temperature alert.
Not writable for Standard Diagnostics version.
TEMPERATURE (1)
Current TEMPERATURE value.
Not writable for Standard Diagnostics version.
ALERT_POINT (2)
-45 to 85 -40
TEMPERATURE Value, below which the ALERT is set to True.
Not writable for Standard Diagnostics version.
DEADBAND (3)
0 - 2
2
TEMPERATURE
change, required to clear the ALERT
,
once it
was set to True.
Not writable for Standard Diagnostics version.
ALERT (4)
FALSE
FALSE
True if the TEMPERATURE has reached below
ALERT_POINT
and have not come above (ALERDEADBAND).
Not writable for Standard Diagnostics version.
HISTORIC ALERT (5)
True -
False
FALSE
True if ALERT is true.
Not changed if ALERT is false.
Not writable for Standard Diagnostics version.
ENABLE (6)
True -
False
TRUE
True - Enables the ALERT
to be reported according to the
configuration.
False - Disables ALERT
reporting.
Not writable for Standard Diagnostics version.
Table 31 Transducer Block Parameters (Continued)
Parameter (in bold)
Sub-parameter (Index)
Range
Initial
Value
Mode
Description
Summary of Contents for Baker Hughes Masoneilan SVI FF
Page 12: ...This page intentionally left blank ...
Page 72: ...This page intentionally left blank ...
Page 82: ...This page intentionally left blank ...
Page 94: ...This page intentionally left blank ...
Page 108: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 224: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...
Page 230: ...This page intentionally left blank ...
Page 250: ...This page intentionally left blank ...
Page 262: ...This page intentionally left blank ...
Page 263: ......