PRESSURE_EXTREMES
(115)
Auto,
Man,
OOS
Minimum and Maximum Pressure values observed since
the last update from the user.
Note: The extremes are evaluated every 0.5 seconds.
Faster changes in the pressure may not be registered.
SUPPLY_PRESSURE_-
MAX (1)
-25 to
1050
-25
SUPPLY_PRESSURE: Maximum value detected since last
update from the user.
SUPPLY_PRES-
SURE_MIN (2)
-25 to
1050
1050
SUPPLY_PRESSURE: Minimum value detected since last
update from the user.
ACTUATOR_A_MAX (3)
-25 to
1050
-25
ACTUATOR_A: Maximum value detected since last update
from the user.
ACTUATOR_A_MIN (4)
-25 to
1050
1050
ACTUATOR_A: Minimum value detected since last update
from the user.
ACTUATOR_B_MAX (5)
-25 to
1050
-25
ACTUATOR_B: Maximum value detected since last update
from the user.
ACTUATOR_B_MIN (86
-25 to
1050
1050
ACTUATOR_B: Minimum value detected since last update
from the user.
PILOT_MAX (7)
-25 to
1050
-25
PILOT_PRESSURE: Maximum value detected since last
update from the user.
PILOT_MIN (8)
-25 to
1050
1050
PILOT_PRESSURE: Minimum value detected since last
update from the user.
TEMPERATURE_
EXTREMES (116)
Auto,
Man,
OOS
Minimum and Maximum Temperature values observed
since the last update from the user.
Note: The extremes are evaluated every 0.5 seconds.
Faster changes in the temperature may not be registered.
TEMPERATURE_MAX (1)
-40 to 85 -40
TEMPERATURE: Maximum value detected since last
update from the user.
TEMPERATURE_MIN (2)
-40 to 85 85
TEMPERATURE: Minimum value detected since last update
from the user.
IP_CURRENT_
EXTREMES (117)
Auto,
Man,
OOS
Minimum and Maximum IP_Current values observed since
the last update from the user.
Note: The extremes are evaluated every 0.5 seconds.
Faster changes in the IP current may not be registered.
IP_CURRENT_MAX (1)
-25 to
150
-25
IP_DRIVE_CURRENT: Maximum value detected since last
update from the user.
IP_CURRENT_MIN (2)
-25 to
150
150
IP_DRIVE_CURRENT: Minimum value detected since last
update from the user.
Table 31 Transducer Block Parameters (Continued)
Parameter (in bold)
Sub-parameter (Index)
Range
Initial
Value
Mode
Description
Summary of Contents for Baker Hughes Masoneilan SVI FF
Page 12: ...This page intentionally left blank ...
Page 72: ...This page intentionally left blank ...
Page 82: ...This page intentionally left blank ...
Page 94: ...This page intentionally left blank ...
Page 108: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 224: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...
Page 230: ...This page intentionally left blank ...
Page 250: ...This page intentionally left blank ...
Page 262: ...This page intentionally left blank ...
Page 263: ......