Device DTM
To switch the device display to
Normal
mode from the device DTM:
1. Open the device DTM and ensure that it is in
Connected
state (Figure 97).
2. Set the TB to Manual mode to avoid valve movement, (1. in Figure 97.).
3. Select
Positioner State
from the DTM Menu (2. in Figure 97).
Figure 97 SVI FF DTM
4. From the
Hardware Group
select
Details . . .
(3. in Figure 97.)
In
Position Control State
group box (at the bottom of the screen) you can see that the
device is being setup from the local display (4. in Figure 98).
Figure 98 Position Control State
5. Press
Set to Normal
(5. in Figure 98) to switch the display back to
Normal
mode and the
positioner follows the setpoint received from Transducer block. You can verify succes by
noting that the TB state is not LO, as in Figure 97