2. TECHNICAL SPECIFICATIONS
GEK-98514B
BUS1000 Busbar Protection
2-3
•
Requirements for Line Current Transformers
•
Relation between the maximum and minimum C.T. ratios in all the positions connected to the
same bus ................................................. 10 maximum
•
Minimum saturation voltage required for main C.T's (for IN = 5 amps)
100 V
•
Intermediate Current Transformers: Normal ratios 5/2-1.33-1-0.5-0.2. Other ratios, including
multiple ratios are available according to application.
•
Stabilization Resistance:
250 Ohms.
•
Restraint Percentage: Adjustable form 0.5 to 0.8 in 0.1 steps
•
Sensitivity: (for internal faults):
Adjustable form 0.2 to 2.0 amps
•
Operation time (output relay included): Below 10 milliseconds
•
Alarm Unit:
Operation threshold: 0.027 Amps.
Operation time: 10 Seconds.
•
Short-circuit link for coupling currents: operation time adjustable between 100 and 1600
milliseconds.
•
Line Trip Supervision Units (optional)
•
Independent Units: Operation threshold between 0.2 and 3.3 amps
•
Dependent units: Operation threshold between 25 and 100% of the breaker failure unit
adjustment.
•
Breaker failure units (optional):
Operation threshold between 0.2 and 3.3 amps
Reset time below 12 milliseconds
Discrimination time between 100 and 730 milliseconds
•
Infeed Source: 125 VDC. Amps systems consumption in mA.
Normal
Tripped
Single bus system
280
670
Trip output (per position)
-
65
Supervision and breaker
Failure units (per position)
70
140
•
Trip contacts:
Make and carry for trip cycle (according to ANSI C37.90)........30 amps
Break: Resistive 180 VA at 125/250 VDC.
Break: Inductive 60 VA at 125/250 VDC.
•
Accuracy:
Operation current:
5%
Operation time:
5%
Summary of Contents for BUS1000
Page 6: ......
Page 8: ......
Page 34: ...5 HARDWARE DESCRIPTION 5 10 BUS1000 Busbar Protection GEK 98514B ...
Page 36: ...6 RECEIVING HANDLING AND STORAGE 6 2 BUS1000 Busbar Protection GEK 98514B ...
Page 54: ...8 FINAL INSTALLATION AND COMMISSIONING 8 4 BUS1000 Busbar Protection GEK 98514B ...
Page 56: ...9 TESTS AND PERIODICAL MAINTENANCE 9 2 BUS1000 Busbar Protection GEK 98514B ...
Page 66: ...10 FIGURES 10 10 BUS1000 Busbar Protection GEK 98514B ...
Page 74: ...11 DIMENSIONS 11 8 BUS1000 Busbar Protection GEK 98514B FIGURE 23 CABINET 226B2211F21 ...
Page 104: ...13 SCHEMATICS DOUBLE BUSBAR 13 16 BUS1000 Busbar Protection GEK 98514B ...