CB Watch 3 User Manual
v6.3 - May 2019
Page 14 of 100
Access Levels
Access to the HMI and the data is restricted according to several username login levels,
each protected by passwords. The various increasing levels of access are listed below.
Each next level has the rights of the preceding level plus those listed:
1
Username:
“u
ser
”
Default password: leave blank
Access to all measurements and parameters is read-only
It is possible to change the language of the HMI
2
Username:
“s
upervisor
”
Default password:
“supervisor”
Only parameters for setting alarms are adjustable
It is possible to download parameters file
3
Username:
“s
pecialist
”
Default password:
“s
pecialist
”
All of the parameters relative to the application are adjustable
In particular all those required for setting up the system
Language
Once you have access to the HMI of the CBW3, the language tab enables you to select
the language that the HMI will use. Click on the required flag first and then click on any
section of the top toolbar, the language will automatically change.
Figure 11
–
HMI language selection
Navigation
Navigation through the menus is done by:
(1)
Selecting one the menu
section
in the toolbar
-
Measurements
-
Settings
-
System
-
Overview
-
Language