Required data (without travel sensor present)
As seen in Section 4.2.5, the following distances (in mm) are required by the system to
calculate the contact separation speed:
O
Start of open position
~ location of 52b sensor (ON when CB is OPEN)
C
Start of close position
~ location of 52a sensor (ON when CB is CLOSED)
Look at old timing test charts to ascertain how far they are located (travel distance when
52b contact changes state). Typically, O will be between 10-15mm (~10% of the total
travel stroke) and C will be at ~90% of total travel stroke. Example: if stroke 135mm, C:
~120mm.
The difference (C-O) will be equivalent to ~80% of the total travel stroke and will
determine the “distance travelled” during the opening or
closing operation used to
calculate the contact separation and touching speed:
Contact separation speed = distance travelled / opening travel time
Contact touching speed = distance travelled / closing travel time
Required data (with travel sensor present)
When a travel sensor is present and used, the following distances (in mm) are required by
the system. The timing is measured when the travel sensor reaches these positions:
A: Open position
Always “0mm” as we start measuring from that position
It is not required to enter that value
B: Open position limits
Tolerance on the open position
Usually set to -5mm (min) and +5mm (max)
C: Start of open position
Same as in previous section above
D: Separation of contact
From open position to middle of arcing contact wipe range.
Found in the CB manual. Example: 25mm
E: Start of close position
Same as in previous section above
F: Closed position limits
Found in the CB manual. Example 195-202mm.
Mid-point is 198 -3mm/+4mm
The mid-point becomes the closed position and the
tolerances become the closed position limits
G: Closed position
Full stroke of CB