CB Watch 3 User Manual
v6.3 - May 2019
Page 71 of 100
Pneumatic/hydraulic Pressure
Pump operation time
There is usually only one large AC powered compressor/pump to generate the
pneumatic or hydraulic pressure, but the number of motors/pumps can be configured to
either 1 or 3 using the drop-down selector:
HMI: Measurement / Settings / Pump
Figure 114
–
Number of pumps setup
This compressor motor is controlled by a pressure sensor, but by connecting a relay in
parallel to the motor AC supply, we can generate motor on/off signals to acquire the
date/time at which these contacts are activated. We can therefore timestamp when the
compressor pump operates and measure the duration of its operation.
HMI: Measurements / Pump
Figure 115
–
Pump run time
The pump run time is measured for comparison purposes and to spot if the compressor
is needing more time to restore the desired pressure, a possible indication of pump
problem. But the results can be affected if the CB is operated at the same time as the
compressor is trying to restore pressure.
The cumulated pump run time is also displayed so that maintenance of the pump(s) can
be performed when the prescribed number of run time hours has been reached.
Because the pump motor only starts whenever the pressure in the storage tank falls
below a certain level and this depends on the number and types of operations previously
performed, it is difficult to predict when the pump will operate. What is key is that the
pump should not operate if no CB operations were performed, as the only reason for the
pressure to drop and require the pump to operate would be a leak in the system.
Therefore, resetting every day at midnight, we also report in the HMI:
-
The number of pump operations in the last 24 hours
-
The number of CB operations in the last 24 hours
-
The total pump run time in the last 24 hours