MA-037 - CB Watch 3 Operating Manual
v7.0 - May 2020
Page 66 of 118
HMI: Measurements / last opening results
Figure 99
–
Contact electrical wear cumulative value
When the arcing contacts are replaced with new ones, the cumulative arcing contact wear
needs to be reset to zero here:
HMI: Settings / Opening
Figure 100
–
Initial electrical wear setting
Contact wear alarm
To receive a warning when we are approaching the time when the arcing contacts need to
be replaced due to wear, a comparison is made between the cumulative electrical wear and
the maximum value specified by the manufacturer of the arcing contacts used.
Alarms can be set per pole and with two threshold values:
-
Threshold 1: a warning level (approaching contact wear limit)
-
Threshold 2: an alarm level (contacts need to be replaced)
HMI: Settings / Opening
Figure 101
–
Opening electrical wear thresholds
Any alarm raised can be seen in the HMI:
HMI: Measurements / Alarms
Figure 102
–
Arcing contact electrical wear alarms