MA-037 - CB Watch 3 Operating Manual
v7.0 - May 2020
Page 81 of 118
The alarms can be seen in the HMI:
HMI: Measurements / Alarms
Figure 134
–
Spring motor run time alarms
Rewind motor current
The CBW3 can measure the current used by the spring rewinding motor (usually a DC
motor) in order to notice any change over time, possibly highlighting additional friction in
the spring mechanism requiring more torque or a problem with the motor itself.
Both the mean (average) motor current and the maximum motor current (peak inrush
current) are recorded and displayed in the HMI:
HMI: Measurements / Last closing results
Figure 135
–
Spring rewind motor current data
An alarm can be set on the maximum inrush current value of the motor by setting a
“Max
threshold” value.
HMI: Settings / Analog channels
Figure 136
–
Spring rewind motor current alarm threshold
The alarm is displayed when the threshold has been reached or exceeded:
HMI: Measurement / Alarms
Figure 137
–
Spring rewind motor current alarm setting