CB Watch 3 User Manual
v6.3 - May 2019
Page 20 of 100
HMI: Measurements/Last opening results or Last closing results
Figure 23
–
Auxiliary contact timing
•
Auxiliary contact 52a switching time: Time elapsed between open/close
command received and the 52a contact changing status
•
Auxiliary contact 52b switching time: Time elapsed between open/close
command received and the 52b contact changing status
A graph is available showing the contact status change for each pole:
HMI: Measurements/Operations Charts/Opening and Closing
Figure 24
–
Auxiliary contact opening and closing graphs
An
“Aux contacts timeout”
maximum threshold value can be entered during setup under.
HMI: Settings/Operations Monitoring
Figure 25
–
Auxiliary contacts switching threshold
An alarm is raised if, after an operation request has been detected, the 52a/52b contacts
do not switch status before the auxiliary contact timeout threshold has been exceeded.
This could indicate a faulty contact or an inability for the CB to respond to an operation
command
(“order rejection”)
.
HMI: Measurements/Alarms
Figure 26
–
Monitoring the auxiliary contacts