If not enough data is available to fill the short term or long term horizon set, then the
value cannot be calculated and a “
-
“ is displayed instead.
HMI: Measurements/Gas
Figure 61
–
Gas leak rates (ganged CB)
Figure 62
–
Gas leak rates (IPO CB)
Gas alarms
Two alarms can be set on the extrapolated gas pressure values calculated. They rely on
the thresholds set in section 5.2.2 above:
•
The
“
long-term
”
alarm is raised if the extrapolated gas pressure at 20
o
C is
calculated to drop below the gas threshold 1 (nearly too low) that has been set
➢
This means that the gas pressure/level will be below threshold 1 within the
long-term horizon that has been set
•
The
“
short-term
”
alarm is raised if the extrapolated gas pressure at 20
o
C is
calculated to drop below the gas threshold 2 (too low, lock-out) that has been set
➢
This means that the gas pressure/level will be below threshold 2 within the
short-term horizon that has been set
HMI: Measurements/Alarms
Figure 63
–
Gas alarms
Gas measurement history
On the HMI, you can view graphs displaying the history of the key gas parameters. Using
the drop down menu, you can select either:
•
Short term graphs: with resolution of 1 value every 10 minutes
•
Long term graphs: with resolution of 1 value per day