CB Watch 3 User Manual
v6.3 - May 2019
Page 68 of 100
HMI: Measurement / Alarms
Figure 110
–
Spring rewind motor current alarm setting
Spring operations charts
The motor current data is recorded for up to 12 seconds and a curve of current over time
is graphed, displayed on the HMI and stored for future comparison:
HMI: Measurement / Operations charts / Spring
Via the HMI, the user is also able to display the previous curves saved in the CBW3:
Figure 111
–
Drop-down list of previous archives
In addition, the following historical graphs are also available:
-
History of mean current value measured
-
History of maximum current value measured
-
History of spring rewinding time measured
-
History of outside ambient temperature when these measurements were made