GEH-6639
——————— INSTRUCTION MANUAL ————————
12
2.4 DESCRIPTION OF CONTROL TERMINALS
Terminals
Function
Voltage, Current
23
Input of the precharge enable control
(15 - 35V, 5 - 11mA)
32
Output of the MLP static signal (low - active signal)
(5 … 35V, 20mA source)
33
(Common) Ground of the MLP and ML static signals
-
34
Reference point for Power 24V
-
35
Power supply 24V
(32V / 300mA max)
36
Output of the ML signal (low - active signal)
(5 … 35V, 20mA max sink)
37
Power supply of the ML and MLP signals
(35V max)
52
(Common) Ground of the precharge enable control
-
70, 72
OK Relay
(max 250V, 1A – AC11)
cs020
2.5 PROTECTIONS
2.5.1 Internal Protection Components
Converter
Designation
Varistors
6KCS3185-480
6KCS3280-480
6KCS3420-480
575 V / 220 J
6KCS3650-480
Ø 20 mm
6KCS310H-480
6KCS315H-480
cs025
V1, V2, V3
2.5.2 Internal Fuses
Converter
Designation
Fuses
Designation
Fuses for
Fuses
6KCS3185-480
6KCS3280-480
16 A / 500 V
6KCS3420-480
fast 6 x 32 mm
6KCS3650-480
6KCS310H-480
25 A / 500 V
6KCS315H-480
fast 6 x 32 mm
cs030
F1, F2, F3
F4
Power supply protection 4 A, 250 V fast 6,3 x 32
F5
+24V protection
1 A, 250 V slow 5 x 20