GE Multilin
D30 Line Distance Protection System
5-21
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.4 CLEAR RELAY RECORDS
PATH: SETTINGS
PRODUCT SETUP
CLEAR RELAY RECORDS
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma-
ble pushbuttons to clear specific records are typical applications for these commands. Since the D30 responds to rising
edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, the following settings should be applied.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the
SETTINGS
PRODUCT SETUP
CLEAR RELAY RECORDS
menu:
CLEAR DEMAND:
“
PUSHBUTTON 1 ON
”
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETTINGS
PRODUCT
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1
menu:
PUSHBUTTON 1 FUNCTION:
“Self-reset”
PUSHBTN 1 DROP-OUT TIME:
“0.20 s”
CLEAR RELAY
RECORDS
CLEAR FAULT REPORTS:
Off
Range: FlexLogic operand
MESSAGE
CLEAR EVENT RECORDS:
Off
Range: FlexLogic operand
MESSAGE
CLEAR OSCILLOGRAPHY?
No
Range: FlexLogic operand
MESSAGE
CLEAR ARC AMPS 1:
Off
Range: FlexLogic operand
MESSAGE
CLEAR ARC AMPS 2:
Off
Range: FlexLogic operand
MESSAGE
RESET UNAUTH ACCESS:
Off
Range: FlexLogic operand
MESSAGE
CLEAR DIR I/O STATS:
Off
Range: FlexLogic operand.
Valid only for units with Direct I/O module.
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...