5-22
D30 Line Distance Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.5 COMMUNICATIONS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
b) SERIAL PORTS
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
SERIAL PORTS
The D30 is equipped with two independent serial communication ports. The faceplate RS232 port is intended for local use
and is fixed at 19200 baud and no parity. The rear COM2 port is RS485. The RS485 port has settings for baud rate and par-
ity. It is important that these parameters agree with the settings used on the computer or other equipment that is connected
to these ports. Any of these ports can be connected to a computer running EnerVista UR Setup. This software can down-
load and upload setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be
daisy-chained and connected to a DCS, PLC, or computer using the RS485 ports.
For the RS485 port, the minimum time before the port transmits after receiving data from a host can be set. This
feature allows operation with hosts which hold the RS485 transmitter active for some time after each transmission.
c) ETHERNET NETWORK TOPOLOGY
The three independent UR ports do not have routing capability and work only on local subnets for the switched network
topology. End nodes can communicate with each other using all supported protocols of the UR family on a local network. In
a routed network, it is recommended to upgrade the UR device used to 7.1x or higher where routing capability through
static route settings has been introduced.
When using more than one Ethernet port, configure each to belong to a different network or subnet using the IP addresses
and mask, else communication becomes unpredictable when more than one port is configured to the same subnet.
COMMUNICATIONS
SERIAL PORTS
See below.
MESSAGE
NETWORK
MESSAGE
MODBUS PROTOCOL
MESSAGE
DNP PROTOCOL
MESSAGE
DNP / IEC104
POINT LISTS
MESSAGE
IEC 61850 PROTOCOL
MESSAGE
WEB SERVER
HTTP PROTOCOL
MESSAGE
TFTP PROTOCOL
MESSAGE
IEC 60870-5-104
PROTOCOL
SERIAL PORTS
RS485 COM2 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
MESSAGE
RS485 COM2 PARITY:
None
Range: None, Odd, Even
MESSAGE
RS485 COM2 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10
NOTE
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...