5-32
D30 Line Distance Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
IEC 61850 messaging can form part of protection schemes. Consider 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing 61850 messaging, it
can be desirable to route 61850 traffic on a separate port from SCADA communications, or to use redundant, inde-
pendent ports, and a high speed network recovery method, such as PRP.
The D30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The D30 operates as an IEC 61850 server. The
Remote inputs and outputs
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
The main transmission menu is shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state
heartbeat
time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
setting is applicable to GSSE, fixed D30 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
GSEE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
GSSE / GOOSE
CONFIGURATION
TRANSMISSION
MESSAGE
RECEPTION
TRANSMISSION
GENERAL
MESSAGE
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
GOOSE
GENERAL
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
Range: 1 to 60 s in steps of 1
GSSE
GSSE FUNCTION:
Enabled
Range: Enabled, Disabled
MESSAGE
GSSE ID:
GSSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
NOTE
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...