5-38
D30 Line Distance Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
RECEPTION
CONFIGURABLE GOOSE
CONFIGURABLE GOOSE 1(16)
CONFIG GSE 1(32) DATA ITEMS
The configurable GOOSE settings allow the D30 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful for
intercommunication between D30 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between D30 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a D30 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and
“GGIO3.ST.Ind2.stVal”. The D30 will then create a dataset containing these two data items. The Boolean status values from
these data items can be utilized as remote input FlexLogic operands. First, the
REMOTE DEVICE 1(16) DATASET
setting must
be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then
REMOTE IN 1(16) ITEM
settings must be
set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic operands will then change state in accordance
with the status values of the data items in the configured dataset.
Double-point status values may be included in the GOOSE dataset. Received values are populated in the
GGIO3.ST.IndPos1.stVal and higher items.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.
Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up).
GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.
CONFIG GSE 1
DATASET ITEMS
ITEM 1:
GGIO3.ST.Ind1.stVal
Range: all valid MMS data item references for
transmitted data
MESSAGE
ITEM 2:
GGIO3.ST.IndPos1.stV
Range: all valid MMS data item references for
transmitted data
MESSAGE
ITEM 3:
None
Range: all valid MMS data item references for
transmitted data
↓
MESSAGE
ITEM 32:
None
Range: all valid MMS data item references for
transmitted data
NOTE
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...