GE Multilin
D30 Line Distance Protection System
5-45
5 SETTINGS
5.2 PRODUCT SETUP
5
k) TFTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
TFTP PROTOCOL
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the D30 over a network. The D30 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The
dir.txt
file
obtained from the D30 contains a list and description of all available files (event records, oscillography, etc.).
When the
TFTP MAIN UDP PORT NUMBER
is set to 0, the change takes effect when the D30 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
l) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
The D30 supports the IEC 60870-5-104 protocol. The D30 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the D30 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the D30 at one time.
TFTP PROTOCOL
TFTP MAIN UDP PORT
NUMBER: 69
Range: 0 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 1
NUMBER: 0
Range: 0 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 2
NUMBER: 0
Range: 0 to 65535 in steps of 1
IEC 60870-5-104
PROTOCOL
IEC 60870-5-104
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
IEC TCP PORT
NUMBER: 2404
Range: 0 to 65535 in steps of 1
MESSAGE
IEC NETWORK
CLIENT ADDRESSES
Range: see sub-menu below
MESSAGE
IEC COMMON ADDRESS
OF ASDU:
0
Range: 0 to 65535 in steps of 1
MESSAGE
IEC CYCLIC DATA
PERIOD:
60 s
Range: 1 to 65535 s in steps of 1
MESSAGE
IEC CURRENT DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC POWER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC ENERGY DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC PF DEFAULT
THRESHOLD: 1.00
Range: 0.00 to 1.00
MESSAGE
IEC OTHER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC REDUNDANCY
ENABLED: No
Range: No, Yes
NOTE
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...