5-116
D30 Line Distance Protection System
GE Multilin
5.5 FLEXLOGIC
5 SETTINGS
5
•
TIMER 1 DROPOUT DELAY:
Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".
5.5.7 FLEXELEMENTS
PATH: SETTING
FLEXLOGIC
FLEXELEMENTS
FLEXELEMENT 1(8)
A FlexElement is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a
net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed
number or its absolute value could be used as per user's choice.
FlexElements run every half power cycle (every four protection passes).
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as
per user's choice.
FLEXELEMENT 1
FLEXELEMENT 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
FLEXELEMENT 1 NAME:
FxE1
Range: up to 6 alphanumeric characters
MESSAGE
FLEXELEMENT 1 +IN:
Off
Range: Off, any analog actual value parameter
MESSAGE
FLEXELEMENT 1 -IN:
Off
Range: Off, any analog actual value parameter
MESSAGE
FLEXELEMENT 1 INPUT
MODE: Signed
Range: Signed, Absolute
MESSAGE
FLEXELEMENT 1 COMP
MODE: Level
Range: Level, Delta
MESSAGE
FLEXELEMENT 1
DIRECTION: Over
Range: Over, Under
MESSAGE
FLEXELEMENT 1
PICKUP: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
FLEXELEMENT 1
HYSTERESIS: 3.0%
Range: 0.1 to 50.0% in steps of 0.1
MESSAGE
FLEXELEMENT 1 dt
UNIT: milliseconds
Range: milliseconds, seconds, minutes
MESSAGE
FLEXELEMENT 1 dt:
20
Range: 20 to 86400 in steps of 1
MESSAGE
FLEXELEMENT 1 PKP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
FLEXELEMENT 1 RST
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
FLEXELEMENT 1 BLK:
Off
Range: FlexLogic operand
MESSAGE
FLEXELEMENT 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
FLEXELEMENT 1
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...