GND DIST Z1 Z0/Z1 MAG:
This setting specifies the ratio between the zero-sequence and positive-sequence imped-
ance required for zero-sequence compensation of the ground distance elements. This setting is available on a per-
zone basis, enabling precise settings for tapped, non-homogeneous, and series compensated lines.
•
GND DIST Z1 Z0/Z1 ANG:
This setting specifies the angle difference between the zero-sequence and positive-
sequence impedance required for zero-sequence compensation of the ground distance elements. The entered value is
the zero-sequence impedance angle minus the positive-sequence impedance angle. This setting is available on a per-
zone basis, enabling precise values for tapped, non-homologous, and series-compensated lines.
•
GND DIST Z1 ZOM/Z1 MAG:
The ground distance elements can be programmed to apply compensation for the zero-
sequence mutual coupling between parallel lines. If this compensation is required, the ground current from the parallel
line (3I_0) measured in the direction of the zone being compensated must be connected to the ground input CT of the
CT bank configured under the
DISTANCE SOURCE
. This setting specifies the ratio between the magnitudes of the mutual
zero-sequence impedance between the lines and the positive-sequence impedance of the protected line. It is impera-
tive to set this setting to zero if the compensation is not to be performed. Note that internally the mutual coupling com-
pensation is applied only if 3I_0>1.22*IG to ensure that no mutual coupling compensation is applied when the fault is
837769A1.CDR
X
R
RE
A
C
H
RCA
DIR RCA
DIR COMP LIMIT
DIR COMP LIMIT
COMP LIMIT
COMP LIMIT
RGT BLD RCA
LFT BLD RCA
RGT BLD
-LFT BLD
"+" NON-HOMOGEN. ANG
"-" NON-HOMOGEN. ANG
837770A1.CDR
X
R
R
EAC
H
RCA
RGT BLD RCA
LFT BLD RCA
RGT BLD
-LFT BLD
RE
V
RE
ACH
REV REACH
RCA
COMP LIMIT
COMP LIMIT
"-" NON-HOMOGEN. ANG
"+" NON-HOMOGEN. ANG
COMP LIMIT
COMP LIMIT
"-" NON-HOMOGEN. ANG
"+" NON-HOMOGEN. ANG
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...