GE Multilin
D30 Line Distance Protection System
5-141
5 SETTINGS
5.6 GROUPED ELEMENTS
5
5.6.5 POWER SWING DETECT
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
POWER SWING DETECT
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2
MESSAGE
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
MESSAGE
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
MESSAGE
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SWING FWD
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING FWD
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING REV
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING OUTER
LIMIT ANGLE: 120°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING MIDDLE
LIMIT ANGLE: 90°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING INNER
LIMIT ANGLE: 60°
Range: 40 to 140° in steps of 1
MESSAGE
POWER SWING OUTER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING OUTER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING MIDDLE
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING MIDDLE
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING INNER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...