a) CYBERSENTRY SECURITY SETTINGS
CyberSentry security settings are configured under
Device > Settings > Product Setup > Security
.
Figure 8–3: CYBERSENTRY SECURITY PANEL
The following settings are available.
RADIUS Server Settings
SETTING NAME
DESCRIPTION
MIN
MAX
DEFAULT
UNITS MINIMUM
PERMISSION
Primary RADIUS IP
Address
IP address of the main RADIUS server.
Default value indicates no Primary
RADIUS server is configured, and hence
RADIUS is disabled.
0.0.0.0
255.255.255.255 0.0.0.0
-
Administrator
Primary
Authentication Port
RADIUS authentication port
1
65535
1812
-
Administrator
Primary Accounting
Port
RADIUS accounting port
1
65535
1813
-
Administrator
Vendor ID
An identifier that specifies RADIUS
vendor-specific attributes used with the
protocol
Value that
represents
General
Electric
Administrator
RADIUS
Authentication
(Shared) Secret
Shared secret used in authentication. It
displays as asterisks. This setting must
meet the CyberSentry password
requirements.
See the
following
password
section for
requirements
255 characters
N/A
-
Administrator
RADIUS
Authentication
Method
Authentication method used by RADIUS
server. Currently fixed to EAP-TTLS.
EAP-TTLS
EAP-TTLS
EAP-TTLS -
Administrator
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...