B-12
D30 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
15FB
Field Contact Output Physical States (8 items)
0 to 65535
---
1
F500
0
1603
Field Shared Input States
0 to 65535
---
1
F500
0
1604
Field Shared Input Channel States
0 to 65535
---
1
F500
0
1605
Field Shared Input Test States
0 to 65535
---
1
F500
0
1606
Field Shared Output Operand States
0 to 65535
---
1
F500
0
1607
Field Latching Output Open Operand States
0 to 65535
---
1
F500
0
1608
Field Latching Output Close Operand States
0 to 65535
---
1
F500
0
1609
Field Latching Output Open Driver States
0 to 65535
---
1
F500
0
160A
Field Latching Output Close Driver States
0 to 65535
---
1
F500
0
160B
Field Latching Output Physical States
0 to 65535
---
1
F500
0
160C
Field Unit Online/Offline States
0 to 65535
---
1
F500
0
160D
Field RTD Input Trouble States
0 to 65535
---
1
F500
0
160E
Field Transducer Input Trouble States
0 to 65535
---
1
F500
0
Ethernet Fibre Channel Status (Read Only)
1610
Ethernet Primary Fibre Channel Status
0 to 2
---
1
F134
0 (Fail)
1611
Ethernet Secondary Fibre Channel Status
0 to 2
---
1
F134
0 (Fail)
1612
Ethernet Tertiary Fibre Channel Status
0 to 2
---
1
F134
0 (Fail)
Field Unit RTD Actuals (Read Only) (8 modules)
16C0
Field RTD x Value
-32768 to 32767
°C
1
F002
0
16C1
...Repeated for module number 2
16C2
...Repeated for module number 3
16C3
...Repeated for module number 4
16C4
...Repeated for module number 5
16C5
...Repeated for module number 6
16C6
...Repeated for module number 7
16C7
...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 modules)
16C8
Field Transducer 1 Value
-32.768 to 32.767
---
0.001
F004
0
16CA
...Repeated for Field Transducer 2
16CC
...Repeated for Field Transducer 3
16CE
...Repeated for Field Transducer 4
16D0
...Repeated for Field Transducer 5
16D2
...Repeated for Field Transducer 6
16D4
...Repeated for Field Transducer 7
16D6
...Repeated for Field Transducer 8
Source Current (Read Only) (2 modules)
1800
Source 1 Phase A Current RMS
0 to 999999.999
A
0.001
F060
0
1802
Source 1 Phase B Current RMS
0 to 999999.999
A
0.001
F060
0
1804
Source 1 Phase C Current RMS
0 to 999999.999
A
0.001
F060
0
1806
Source 1 Neutral Current RMS
0 to 999999.999
A
0.001
F060
0
1808
Source 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
180A
Source 1 Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
180B
Source 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
180D
Source 1 Phase B Current Angle
-359.9 to 0
degrees
0.1
F002
0
180E
Source 1 Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
1810
Source 1 Phase C Current Angle
-359.9 to 0
degrees
0.1
F002
0
1811
Source 1 Neutral Current Magnitude
0 to 999999.999
A
0.001
F060
0
1813
Source 1 Neutral Current Angle
-359.9 to 0
degrees
0.1
F002
0
1814
Source 1 Ground Current RMS
0 to 999999.999
A
0.001
F060
0
1816
Source 1 Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1818
Source 1 Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1819
Source 1 Zero Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181B
Source 1 Zero Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181C
Source 1 Positive Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
Table B–10: MODBUS MEMORY MAP (Sheet 4 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...