GE Multilin
D30 Line Distance Protection System
B-25
APPENDIX B
B.4 MEMORY MAPPING
B
409C
DNP Address
0 to 65519
---
1
F001
1
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus Protocol
0 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
0 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
0 to 65535
---
1
F001
80
40A6
Main UDP Port Number for the TFTP Protocol
0 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP Unsolicited Responses Maximum Retries
1 to 255
---
1
F001
10
40AC
DNP Unsolicited Responses Destination Address
0 to 65519
---
1
F001
1
40AD
Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
40AE
DNP Current Scale Factor
0 to 8
---
1
F194
2 (1)
40AF
DNP Voltage Scale Factor
0 to 8
---
1
F194
2 (1)
40B0
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B1
DNP Energy Scale Factor
0 to 8
---
1
F194
2 (1)
40B2
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B3
DNP Other Scale Factor
0 to 8
---
1
F194
2 (1)
40B4
DNP Current Default Deadband
0 to 100000000
---
1
F003
30000
40B6
DNP Voltage Default Deadband
0 to 100000000
---
1
F003
30000
40B8
DNP Power Default Deadband
0 to 100000000
---
1
F003
30000
40BA
DNP Energy Default Deadband
0 to 100000000
---
1
F003
30000
40BC
DNP Power Factor Default Deadband
0 to 100000000
--
1
F003
30000
40BE
DNP Other Default Deadband
0 to 100000000
---
1
F003
30000
40C0
DNP IIN Time Synchronization Bit Period
1 to 10080
min
1
F001
1440
40C1
DNP Message Fragment Size
30 to 2048
---
1
F001
240
40C2
DNP Client Address 3
0 to 4294967295
---
1
F003
0
40C4
DNP Client Address 4
0 to 4294967295
---
1
F003
0
40C6
DNP Client Address 5
0 to 4294967295
---
1
F003
0
40C8
DNP Number of Paired Binary Output Control Points
0 to 32
---
1
F001
0
40C9
DNP TCP Connection Timeout
10 to 7200
s
1
F001
120
40CA
DNP Communications Reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
0 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 Protocol Function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 Protocol Cyclic Data Transmission Period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 Current Default Threshold
0 to 100000000
---
1
F003
30000
40E6
IEC 60870-5-104 Voltage Default Threshold
0 to 100000000
---
1
F003
30000
40E8
IEC 60870-5-104 Power Default Threshold
0 to 100000000
---
1
F003
30000
40EA
IEC 60870-5-104 Energy Default Threshold
0 to 100000000
---
1
F003
30000
40EC
IEC 60870-5-104 Power Factor Default Threshold
0 to1
---
0.01
F001
100
40EE
IEC 60870-5-104 Other Default Threshold
0 to 100000000
---
1
F003
30000
40F0
IEC 60870-5-104 Client Address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 Redundancy Port Enabled/Disabled
0 to 1
---
1
F126
0 (No)
4105
Port 2 IP Address
0 to 4294967295
---
1
F003
56554706
4107
Port 2 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4109
Port 2 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
410B
PRT2 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
410C
PRT2 Redundancy Enabled
0 to 1
---
1
F126
0 (No)
410D
Port 3 IP Address
0 to 4294967295
---
1
F003
56554706
410F
Port 3 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4111
Port 3 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
4113
Port 3 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
Table B–10: MODBUS MEMORY MAP (Sheet 17 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...