2-20
D30 Line Distance Protection System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.2.11 TYPE TESTS
D30 TYPE TESTS
2.2.12 PRODUCTION TESTS
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
TEST
REFERENCE STANDARD
TEST LEVEL
Dielectric voltage withstand
EN 60255-5
2.2 kV
Impulse voltage withstand
EN 60255-5
5 kV
Damped oscillatory
IEC 61000-4-18 / IEC 60255-22-1
2.5 kV CM, 1 kV DM
Electrostatic discharge
EN 61000-4-2 / IEC 60255-22-2
Level 3
RF immunity
EN 61000-4-3 / IEC 60255-22-3
Level 3
Fast transient disturbance
EN 61000-4-4 / IEC 60255-22-4
Class A and B
Surge immunity
EN 61000-4-5 / IEC 60255-22-5
Level 3 and 4
Conducted RF immunity
EN 61000-4-6 / IEC 60255-22-6
Level 3
Power frequency immunity
EN 61000-4-7 / IEC 60255-22-7
Class A and B
Voltage interruption and ripple DC
IEC 60255-11
12% ripple, 200 ms interrupts
Radiated and conducted emissions
CISPR11 / CISPR22 / IEC 60255-25
Class A
Sinusoidal vibration
IEC 60255-21-1
Class 1
Shock and bump
IEC 60255-21-2
Class 1
Seismic
IEC 60255-21-3
Class 1
Power magnetic immunity
IEC 61000-4-8
Level 5
Pulse magnetic immunity
IEC 61000-4-9
Level 4
Damped magnetic immunity
IEC 61000-4-10
Level 4
Voltage dip and interruption
IEC 61000-4-11
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory
IEC 61000-4-12
2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz
IEC 61000-4-16
Level 4
Voltage ripple
IEC 61000-4-17
15% ripple
Ingress protection
IEC 60529
IP40 front, IP10 back
Cold
IEC 60068-2-1
–40°C for 16 hours
Hot
IEC 60068-2-2
85°C for 16 hours
Humidity
IEC 60068-2-30
6 days, variant 1
Damped oscillatory
IEEE/ANSI C37.90.1
2.5 kV, 1 MHz
RF immunity
IEEE/ANSI C37.90.2
20 V/m, 80 MHz to 1 GHz
Safety
UL 508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
Safety
UL 1053
e83849 NKCR
Safety
IEC 60255-27
Insulation: class 1, Pollution degree: 2, Over
voltage cat II
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...
Page 646: ...x D30 Line Distance Protection System GE Multilin INDEX...