B-40
D30 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
778E
Thermal Protection 1 Minimum Reset Time
0 to 1000
min.
1
F001
20
778F
Thermal Protection 1 Reset
0 to 4294967295
---
1
F300
0
7791
Thermal Protection 1 Block
0 to 4294967295
---
1
F300
0
7793
Thermal Protection 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7794
Thermal Protection 1 Events
0 to 1
---
1
F102
0 (Disabled)
7795
Reserved (2 items)
---
---
---
F001
0
7797
Repeated for Thermal Protection 2
Broken Conductor Detection (Read/Write Settings) (2 modules)
77AA
Broken Conductor 1 Function
0 to 1
---
1
F102
0 (Disabled)
77AB
Broken Conductor 1 Source
0 to 5
---
1
F167
0 (SRC 1)
77AC
Broken Conductor 1 I2/I1 Ratio
20 to 100
%
0.1
F001
200
77AD
Broken Conductor 1 I1 Minimum
0.05 to 1
pu
0.01
F001
10
77AE
Broken Conductor 1 I1 Maximum
0.05 to 5
pu
0.01
F001
150
77AF
Broken Conductor 1 Pickup Delay
0 to 65.535
s
0.001
F001
20000
77B0
Broken Conductor 1 Block
0 to 4294967295
---
1
F300
0
77B2
Broken Conductor 1 Target
0 to 2
---
1
F109
0 (Self-reset)
77B3
Broken Conductor 1 Events
0 to 1
---
1
F102
0 (Disabled)
77B4
Reserved (2 items)
---
---
---
F001
0
77B6
...Repeated for Broken Conductor 2
Ohm Inputs (Read/Write Setting) (2 modules)
77F8
Ohm Inputs 1 Function
0 to 1
---
1
F102
0 (Disabled)
77F9
Ohm Inputs 1 ID
---
---
---
F205
"Ohm Ip 1 "
77FF
Ohm Inputs 1 Reserved (9 items)
0 to 65535
---
1
F001
0
7808
...Repeated for Ohm Inputs 2
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
0 to 2
---
1
F137
0 (Disabled)
7B61
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
7B6B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
7B75
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
7B7F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
7B80
User Programmable Pushbutton 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7B81
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
7B82
User Programmable Pushbutton 1 LED Operand
0 to 4294967295
---
1
F300
0
7B84
User Programmable Pushbutton 1 Autoreset Delay
0.2 to 600
s
0.1
F001
10
7B85
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
7B86
User Programmable Pushbutton 1 Local Lock Operand
0 to 4294967295
---
1
F300
0
7B88
User Programmable Pushbutton 1 Message Priority
0 to 2
---
1
F220
0 (Disabled)
7B89
User Programmable Pushbutton 1 Remote Lock Operand
0 to 4294967295
---
1
F300
0
7B8B
User Programmable Pushbutton 1 Reset Operand
0 to 4294967295
---
1
F300
0
7B8D
User Programmable Pushbutton 1 Set Operand
0 to 4294967295
---
1
F300
0
7B8F
User Programmable Pushbutton 1 Hold
0 to 10
s
0.1
F001
1
7B90
...Repeated for User Programmable Pushbutton 2
7BC0
...Repeated for User Programmable Pushbutton 3
7BF0
...Repeated for User Programmable Pushbutton 4
7C20
...Repeated for User Programmable Pushbutton 5
7C50
...Repeated for User Programmable Pushbutton 6
7C80
...Repeated for User Programmable Pushbutton 7
7CB0
...Repeated for User Programmable Pushbutton 8
7CE0
...Repeated for User Programmable Pushbutton 9
7D10
...Repeated for User Programmable Pushbutton 10
7D40
...Repeated for User Programmable Pushbutton 11
7D70
...Repeated for User Programmable Pushbutton 12
7DA0
...Repeated for User Programmable Pushbutton 13
7DD0
...Repeated for User Programmable Pushbutton 14
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for D30D00HCHF8AH6AM6BP8BX7A
Page 10: ...x D30 Line Distance Protection System GE Multilin TABLE OF CONTENTS...
Page 374: ...5 248 D30 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5...
Page 398: ...6 24 D30 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6...
Page 410: ...7 12 D30 Line Distance Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7...
Page 444: ...9 24 D30 Line Distance Protection System GE Multilin 9 5 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 576: ...B 102 D30 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B...
Page 616: ...D 10 D30 Line Distance Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D...
Page 628: ...E 12 D30 Line Distance Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E...
Page 636: ...F 8 D30 Line Distance Protection System GE Multilin F 3 WARRANTY APPENDIX F F...